FAQ

12
continued from page 11
Devices, Receivers, Transmitters, etc. If you are involved
in this work, please reference Article 726 in this guide
and the actual NEC 70.
Revision
110.21(A)(2) Reconditioned Equipment
Leviton Comment: Article 110.21(A)(2) is covered with
Article 240.2 found on page 53
Revision
110.26 Spaces About
Electrical Equipment
Change Summary
• Revision made to ensure ample space
around equipment.
NEC
®
Text
Article 110 General Requirements for Electrical
Installations
110.26 Spaces About Electrical Equipment.
Working space, and access to and egress from working
space, shall be provided and maintained about all electrical
equipment to permit ready and safe operation and
maintenance of such equipment. Open equipment doors shall
not impede access to and egress from the working space.
Access or egress is impeded if one or more simultaneously
opened equipment doors restrict working space access to be
less than 610 mm (24 in.) wide and 2.0 m (6-1/2 ft) high.
Expert Analysis
A revision has been made to clarify that the requirements
in 110.26(A)(2)(b) be relocated to 110.26, due to the fact
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.