Installation Guide

WARNINGS AND CAUTIONS:
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
• Tobeinstalledand/orusedinaccordancewithelectricalcodesandregulations.
• Ifyouarenotsureaboutanypartoftheseinstructions,consultanelectrician.
• DO NOTcontrolaloadinexcessofthespeciedratings.Damagetotheunit,re,electricshock,personalinjuryordeathcanoccur.
Checkyourloadratingstodeterminesuitabilityforyourapplication.
WARNINGS AND CAUTIONS:
• Use only with LevLok module MSPSW-XST (Stranded wire) or MSPSW-XSD (Solid wire)
• MDS10-IDxisadigitaldevicewithelectroniccomponents,donotterminateLevLokmoduletodevicewithpoweron.
• Donotinstallthisunittocontrolareceptacle.
• Donottouchthesurfaceofthelens.Cleanoutersurfacewithadampclothonly.
• TheCat.No.MDS10-IDxoccupancysensorisintendedtoreplaceastandardlightswitch.
• UsethisdeviceONLY WITH COPPER OR COPPER CLAD WIRE.
SinglePole(OneLocation)orMulti-Location
Designer Wall Switch Occupancy Sensor with LevLok
Cat. No. MDS10-IDx
Incandescent - 800W-6.67A@120V-Fluorescent -1200VA-10A@120V-Fluorescent -2700VA-10A@277V-Supplemental - 1/4hp-5.8A@120V
No Minimum Load Required
Compatiblewithelectronicandmagneticballasts,electronicandmagneticlow-voltageballasts,incandescentlamps,andfans.
INSTALLATION INSTRUCTIONS
TOOLS NEEDED TO INSTALL YOUR SENSOR
Slotted/PhillipsScrewdriver ElectricalTape Pliers
Cutters SmallSlottedScrewdriver
LevitonCat.No.MDS10-IDx,DesignerWallSwitchOccupancy
Sensor,isdesignedtodetectmotionfromaheat-emittingsource
(suchasapersonenteringaroom)withinitseld-of-view(monitored
space)andautomaticallyswitchlightsONandOFF.Thecontrolled
lightswillremainONuntilnomotionisdetectedandthescheduled
time-delayhasexpired.
Cat. No. MDS10-IDx is UL listed, CSA certified and conforms to
California Title 24 requirements.
TheOccupancySensorsensesmotionwithinitscoverageareaof
2100sq.ft(195.1m
2
)maximumandcontrolstheconnectedlighting.
Thisisaself-containeddevicewhichprovidessensingandlight
control.TheOccupancySensorwillturnthelightsONwhenmotion
isinitiallydetected,andkeepthelightsONforaslongasmotionis
detected.
TheOccupancySensorusesasmallsemiconductorheatdetectorthat
residesbehindamulti-zoneopticallens.ThisFresnellensestablishes
dozensofzonesofdetection.Thesensorissensitivetotheheat
emittedbythehumanbody.Inordertotriggerthesensor,thesource
ofheatmustmovefromonezoneofdetectiontoanother.Thedevice
ismosteffectiveinsensingmotionacrossitseld-of-view,andless
effectivesensingmotiontowardsorawayfromitseld-of-view(refer
to Field-of-View diagrams).Keepthisinmindwhenselectingthe
installationlocation(refer to Field-of-View diagrams).
Notethatoccupancysensorsrespondtorapidchangesin
temperature,socareshouldbetakennottomountthedevice
nearaclimatecontrolsource(i.e.radiators,airexchanges,andair
conditioners).Hotorcolddraftswilllooklikebodymotiontothedevice
andwilltriggeritiftheunitismountedtooclose.It is recommended
to mount the Occupancy Sensor at least 6 ft. away from then
climate control source.Thedevicecanbemountedinasinglegang
wallbox.
Inaddition,itisalsorecommendedNOTtomounttheOccupancy
Sensordirectlyunderalargelightsource.Largewattagebulbs
(greaterthan100Wincandescent)giveoffalotofheatandswitching
thebulbcausesatemperaturechangethatcanbedetectedbythe
device.MounttheOccupancySensoratleast6ft.awayfromlarge
bulbs.Ifitnecessarytomountthedevicecloser,lowerthewattageof
thebulbdirectlyoverhead
WARNING:TO AVOID FIRE, SHOCK, OR DEATH; TURN
OFF POWER atcircuitbreakerorfuseandtestthatpoweris
offbeforewiring!
Step 1
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFFONOFF
ONOFF
ONOFF
ONOFF
ONOFF
• Pulloffpre-cutinsulationfromsensorleads.
• Makesurethattheendsofthewiresfromthewallboxarestraight
(cut if necessary).
• Removeinsulationfromeachwireinthewallboxasshown.
Preparing and connecting wires:
9/16"
(1.4 cm)
Strip Gage
(measure bare
wire here)
Cut
(if necessary)
Step 3
INSTALLING YOUR SENSOR
NOTE:UsecheckboxeswhenStepsarecompleted.
Installing your Sensor – Single-Pole Application:
Step 4
Identifying your wiring application
(most common):
Step 2
WIRING SENSOR:
Connect wires per WIRING DIAGRAM as follows:Screwwireconnector
onclockwisemakingsuretherearenobareconductorsbelowthewire
connectors.Secureeachconnectorwithelectricaltape.
• GreenorbarecopperwireinwallboxtoGreenlead.
• LineHotwallboxwiretoBlacklead.
• LoadwallboxwiretoBluelead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.
WIRING SENSOR 1:
Connect wires per WIRING DIAGRAM as follows:
• GreenorbarecopperwireinwallboxtoSensor1Greenlead.
• LineHot(common)wallboxwireidentied(tagged)whenremovingold
switchandFirsttravelerfromSensor2toSensor1Blacklead.
• SecondTravelerwallboxwirefromSensor2toSensor1Bluelead.
WIRING SENSOR 2:
Connect wires per WIRING DIAGRAM as follows:
• GreenorbarecopperwireinwallboxtoSensor2Greenlead.
• Loadwallboxwireidentied(tagged)whenremovingoldswitchand
SecondTravelerfromSensor1toSensor2Bluelead.
• FirstTravelerLineHotfromSensor1toSensor2Blacklead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.
NOTE: Use only with LevLok module MSPSW-XST (Stranded wire)
or MSPSW-XSD (Solid wire).
NOTE: TheCat.No.MDS10-IDxrequiresagroundwiretooperate
properly.Ifthereisnogroundwire,ensureelectricalboxisgroundedand
attachgroundwiretoboxwithascrew.Ifthegroundwireisoatingthis
devicewillnotwork.
NOTE: Use only with LevLok module MSPSW-XST (Stranded wire)
or MSPSW-XSD (Solid wire).
NOTE: TheCat.No.MDS10-IDxrequiresagroundwiretooperate
properly.Ifthereisnogroundwire,ensureelectricalboxisgroundedand
attachgroundwiretoboxwithascrew.Ifthegroundwireisoatingthis
devicewillnotwork.
NOTE:EithersensorcanturnthelightsON.Bothsensorsmusttimeout
toOFForbothmanualbuttonsmustbepressedforthelightstogoOFF.
DESCRIPTION
DI-000-MDS10-02A
• Leviton’sDecora
®
styledesign
• Switcheselectronicballasts
• LowProle,tamper-resistantlens
• AmbientLightOverride
• LevLokquickconnect
FEATURES
3-Way
1. LineorLoad(Seeimportant*instruction)
2. Ground
3. FirstTraveler–notecolor
4. SecondTraveler–notecolor
Single-Pole
1.Line(Hot)
2.Ground
3.Load
IMPORTANT:For3-Wayapplications,notethatoneofthescrew
terminalsfromtheoldswitchbeingremovedwillusuallybeadifferent
color(Black)orlabeledCommon.Tagthatwirewithelectricaltapeand
identifyasthecommon(LineorLoad)inbothswitchwallboxes.
Step 5
Installing your Sensor – 3-Way Wiring Application:
NOTE:Dresswireswithabendtorelievestresswhenmounting
device.
Positionallwirestoprovideroominoutletwallboxfordevice.
• Partiallysecuredeviceusinglongmountingscrewsprovided.
• Restorepoweratcircuitbreakerorfuse.
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becareful
NOTTOOVERTURNthecontrolknobsorleverswhensettingthe
Sensor.Thecontrolscanbeaccessedbyremovingthewallplate
(ifapplicable)andcontrolpanelcover(refer to Control Panel
Diagram).Useasmallstraightbladescrewdrivertoadjustknobs
andandangertoadjusttheblinderlevers.
NOTE: DO NOT pressinonblinderleversoruseexcessiveforce
(refer to Control Panel Diagram).
• AttachtheControlPanelcoverwhenthedesiredsettingsare
complete.
If lights do not turn ON, refer to the TROUBLESHOOTING section.
Testing your Sensor prior to completely
mounting in wall box:
Step 6
Wire Connector
(twist clockwise)
Protective Label
Wall
Module
Wall box
Hot (Black)
Ground (Green)
Load (Blue)
Electrical tape
3. Turn and lock flush 4. Push latch up and turn to release
1. Remove protective label 2. Orient and push
Device Mounting:
TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE.
Step 7
Restore Power:
Restorepoweratcircuitbreakerorfuse.
Installation is complete.
LeavetheroomandthelightswillturnOFFafterthe
selectedtime-outexpires.
Step 8
Installationmaynowbecompletedbytightening
mountingscrewsintowallbox.Attachwallplate.
Hot (Black)
Neutral (White)
Load
Sensor
Black
Black
White
Blue
Green
Ground
Line
120-277VAC
50/60 Hz
Hot
(Black)
Neutral (White)
Load
Blue
Blue
Black
Green
Ground
Black
White
Black
Line
120-277VAC
50/60 Hz
Green
Ground
Sensor 2
Sensor 1