FAQ

84
Sizing Using Nameplate
Leviton Solution
Powerswitch
®
Manual Motor Controllers
Heavy-duty horsepower rated switches capable of providing manual
ON/OFF control to higher motor loads than standard toggle switches.
Built for commercial and industrial installations up to 60 Amps,
Leviton oers a line of industrial grade AC single-phase and
three-phase manual motor controllers with a continuous current
rating at all voltages up to 600V AC and maximum horsepower
ratings of 30HP.
Our 30 Amp and 40 Amp motor switches are UL 508 listed
“Suitable as Motor Disconnect”, which means they may be used in
place of a standard disconnect switch in line-of-sight applications
in factory settings.
Revision
440.11 AC/Refrigeration Disconnect
Requires Lock or Tool to Access
Change Summary
Where the disconnecting means is readily accessible
to an unqualified person per 440.11, a tool to open
is required, or be capable of being locked.
Article 440 – Air-Conditioning and Refrigeration
Equipment
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
continued from page 83