Installation & Operation Guide 400CP WEB VERSION Remote Control Panel
Table of Contents INTRODUCTION ................................................................................................................. 3 IMPORTANT......................................................................................................................... 3 WIRING................................................................................................................................. 3 PROGRAMMING...................................................................................
Introduction The Leviton 400CP represents a key part of a state of the art, total lighting control system. Combined with Leviton dimmers and optionally, a Leviton memory control console, a totally integrated system is achieved. The 400CP can automatically take control of up to 512 dimmer channels. Control is automatically passed between400CP’s and the memory control console as desired. The 400CP is exceptionally easy to operate and features 4zone control with programmable fade times.
MOUNTING The 400CP will mount in any standard double-gang electrical box with the 4 screws provided. See below paragraph on system turn-on before final mounting of panels. SYSTEM TURN-ON It is very important that the system operation be verified one panel at a time or else an improper connection at one panel would cause the entire system to not operate properly and may be difficult to diagnose.
Programming Several parameters must be programmed into the 400CP for it to operate properly: Dimmer channel assignments for each scene. Dimmer levels for each scene. Fade time for each scene. Master / Slave operation. Network ID number (IMPORTANT). Optionally, the unit may be ordered preprogrammed from the factory. Any field modifications can be made if necessary. Factory Default Setting: The 400CP is programmed at the factory for zone 1-4 to be set for channel 1-4 respectively.
Maximum number of dimmers. This parameter must be set to reflect a number greater than or equal to the maximum number of dimmer channels installed in the system. The factory default is 32 dimmer channels. If this number is correct then this step may be ignored. The maximum number of dimmers may be set as follows: 1. Make sure that the 400CP is in the program select mode as discussed. 2. Press the zone 1 increase button and the BUSY led will quit flashing. 3.
Assigning dimmer channels to each scene. Each of the zones of the 400CP must be programmed with the desired dimmer channel assignments. Only the dimmer channels assigned will be affected by each zone’s increase and decrease buttons. In order to easily identify dimmer channels while programming, the system should have all installed lamps or loads operational.
Scene fade time programming. Each zone may be programmed with an individual fade time. This is the time it will take the dimmer channels assigned to go from full off to full on and visa versa. Fade time can vary from 0 to 13 seconds. A longer fade time will increase the accuracy when using the increase and decrease buttons to set desired lighting levels. A fade time of 0 seconds will cause instant full on or full off operation whenever the increase or decrease buttons are pressed.
Master/Slave Mode 400CP panels may be slaved to one another. Several panels may act as slaves to a master panel which contains the programming. The slaves will mimic the master LED’s and will operate the scenes and fade times of the master. This is ideal for installations with several panels in one room. To make a panel into a master (factory default); set the Master\Slave ID to 0. To make a panel into a slave; set the Master/Slave ID to the Network ID of the desired master to slave to.
Network ID number. Since the Luma-Net® System is a digital network, all panels and devices attached (except dimmers) must have a unique network ID number. If two panels have the same network ID number, the entire network will stop functioning. Panels without a dipswitch must follow this procedure otherwise simply set the dipswitch as per the chart on the following page. To set Network ID number (units without dipswitch): 1. Make sure that the 400CP is in the program mode as discussed. 2.
ID number 0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108 111 114 117 120 123 126 12345678 00000000 11000000 01100000 10010000 00110000 11110000 01001000 10101000 00011000 11011000 01111000 10000100 00100100 11100100 01010100 10110100 00001100 11001100 01101100 10011100 00111100 11111100 01000010 10100010 00010010 11010010 01110010 10001010 00101010 11101010 01011010 10111010 00000110 11000110 01100110 10010110 00110110 11110110 01001110 1010111
Operation To raise lighting levels: Press and hold the increase button of the zone desired. The 400cp will then take control of all dimmer channels assigned to the selected zone and increase lighting levels at the programmed fade rate. Release button when correct lighting levels are attained. To lower lighting levels: Press and hold the decrease button of the zone desired.