Installation Guide

Page 7
Assigning dimmer channels to each scene.
Each of the zones of the 400CP must be programmed with the desired dimmer channel
assignments. Only the dimmer channels assigned will be affected by each zone’s increase
and decrease buttons. In order to easily identify dimmer channels while programming, the
system should have all installed lamps or loads operational. If this is not possible, the 400CP
to be programmed should be temporarily connected nearby to the dimmer units so that the
control LEDs of the dimmers may be observed to verify channel selection.
To program each zone:
1. Make sure that the 400CP is in the program select mode as discussed. The BUSY LED
should be flashing.
2. Press the zone 2 increase button to select "dimmer assignment mode" and the BUSY LED
will stop flashing.
3. Press INCREASE button representing desired zone to be programmed. At this point, all
currently assigned dimmers will come on. The current dimmer selector will be set to one.
4. Use the buttons marked as UP and DOWN in diagram to increment or decrement the
dimmer channel selector.
Tap the buttons the required number of times to reach the dimmer channel to be assigned.
5. Use the ADD and DELETE buttons to add or delete this dimmer from the zone. The lamps
connected to this dimmer channel will come on full when the ADD button is pressed.
Observe lamps or dimmer LEDs to verify correct channel has been selected.
6. A new zone can be programmed at any time by pressing the appropriate zone INCREASE
button. The dimmer selector number will always return to one when changing zones.
7. To exit this programming mode; press both the UP and DOWN buttons at the same time.
The BUSY LED will start flashing again when both buttons are then released.