Specification

PRODUCT DATA
ODC Series Multi-Technology Occupancy Sensors
FEATURES
• Industry-exclusive H.I.S. (High Inrush Stability)
technology designed to handle today’s high inrush
electronic ballast loads and offer unmatched durability
and service
• Robust and reliable mechanically held 10A latching
relay provides dependability and robust performance
for all load types and provides energy savings over
electronically held relays
• Field of View: Units from 500 to 2000 square feet
available
• Lenses are easily replaceable and color-coded red
(mid-range) and black (extended range) for contractors
and end-users to easily identify lenses from the ground
• Visual LED indicators for all states:
• Red - Blinks when infrared is detecting motion and
during photocell manual calibration; solid during
device malfunction
• Green - Blinks when U/S is detected; solid during
auto calibration
• Yellow - Blinks during test mode; solid with
emergency/BMS input
RATINGS AND TESTING
• Zero-crossing circuitry for extended life of the relay
• Tested to exceed 1 million switching cycles under
standard loads
• Multiple compliance and regulatory UL testing -
consult factory for details
• Passed rigorous NEMA 410 testing for electronic ballast
rating
• BMS Input/Emergency Override: UL 924 listed for
Emergency and Egress lighting control
• Meets Energy Star® Requirements for multi-techs and
ultrasonics
Photocell Features
• Daylight Harvesting Applications:
Auto-Calibration (Automatic Daylight
Calibration): Photocell intelligently measures
light levels to determine optimal daylight
design levels for closed loop applications
Closed loop: Photocell detects total
photometric light from daylight or electric
sources in the space
Open loop: Photocell detects daylight or
electric light only; requires manual calibration
• Adjustable daylight design levels: Normal (OFF),
Manual (ON/OFF) and Auto Calibration
• Blue - Blinking light indicates photocell override
• Integrated photocell tested to less than 1 Fc
accuracy
• Open and closed loop photocell included
INSTALLATION
• Easy installation into junction boxes with Leviton-
exclusive screw guides, coasters and terminal
blocks
• Front cover snaps on and off for ease of
installation
CLOSED LOOP
Noon
1.25x DDL
Zone ON
2.5x DDL
Zone OFF
Lights ON
DDL
Dawn
0
1
2
3
4
5
6
7
Dusk
Closed Loop - Flat Light Pipe
PHOTOCELL PLACEMENT*
Window
Peak Sensitivity
68°
ODC
Typical Daylit Zone, about 10’
Light Fixture
9’
4’
Closed Loop Application - Flat Light Pipe
Peak
Sensitivity
ODC
Light Fixture
9’
45°
4’
Open Loop Application - Angled Light Pipe
OPEN LOOP
Noon
ON trigger point
Lights turn ON
OFF trigger point
Lights turn OFF
DDL
Lights ON
Night time
Dawn
0
1
2
3
4
5
6
7
Dusk
PHOTOCELL OPERATION
Note: Long side of angled light pipe must
face toward natural light source (window)
Open Loop - Angled Light Pipe
*May require more than one occupancy sensor for total room coverage