Specification

PRODUCT DATA
ODC Series Ultrasonic Occupancy Sensors
FEATURES
• Robust and reliable mechanically held 10A latching
relay provides dependability and robust performance
for all load types and provides energy savings over
electronically held relays
• Field of View: Units from 500 to 2000 square feet
available
• Visual LED indicators for all states:
Green - Blinks during U/S detection and is solid
during auto-calibration
Yellow - Blinks during test mode; solid with
emergency/BMS input
Blue - Blinks when knob settings are changed and
during photocell override
RATINGS AND TESTING
•Zero-crossing circuitry for extended life of the relay
• Tested to exceed 1 million switching cycles under
standard loads
• Multiple compliance and regulatory UL testing - con-
sult factory for details
• Passed rigorous NEMA 410 testing for electronic
ballast rating
• BMS Input/Emergency Override: UL 924 listed for
Emergency and Egress lighting control
• Meets Energy Star® Requirements for multi-tech
and ultrasonics
Photocell Features
• Daylight Harvesting Applications:
Auto-Calibration (Automatic Daylight
Calibration): Photocell intelligently measures
light levels to determine optimal daylight
design levels for closed loop applications
Closed loop: Photocell detects total
photometric light from natural light or
electric sources in the space
• Open loop: Photocell detects daylight or
electric light only; requires manual calibration
• Adjustable daylight design levels: Normal (OFF),
Manual (ON/OFF) and Auto Calibration
• Integrated photocell tested to less than 1 Fc
accuracy
• Open and closed loop photocell included
INSTALLATION
• Easy installation into junction boxes with Leviton-
exclusive screw guides, coasters and terminal
blocks
• Front cover snaps on and off for ease of
installation
OPEN LOOP
Noon
ON trigger point
Lights turn ON
OFF trigger point
Lights turn OFF
DDL
Lights ON
Night time
Dawn
0
1
2
3
4
5
6
7
Dusk
PHOTOCELL OPERATION
CLOSED LOOP
Noon
1.25x DDL
Zone ON
2.5x DDL
Zone OFF
Lights ON
DDL
Dawn
0
1
2
3
4
5
6
7
Dusk
Closed Loop - Flat Light Pipe
Note: Long side of angled light pipe must
face toward natural light source (window)
PHOTOCELL PLACEMENT*
Window
Peak Sensitivity
68°
ODC
Typical Daylit Zone, about 10’
Light Fixture
9’
4’
Closed Loop Application - Flat Light Pipe
Peak
Sensitivity
ODC
Light Fixture
9’
45°
4’
Open Loop Application - Angled Light Pipe
Open Loop - Angled Light Pipe
*May require more than one occupancy sensor for total room coverage