Specification

PRODUCT DATA
ODS0D
ing tape required.
• Time delay adjustment for delayed-OFF time settings of
30 seconds, 5, 10, and 30 minutes. Allows customized
adjustments to maximize energy savings.
• Vandal resistant PIR lens.
• False detection circuitry.
• Light Sensor adjustable Ambient Light Override ranges
from approximately 2FC (20 LUX) to 500+FC (5000+ LUX).
Manual-ON/auto-OFF mode for installations where manual-
ON switching is required but auto-OFF switching is still
desired for CEC Title T24 energy savings.
To comply with CEC Title 24, red LED indicator light flashes
when PIR sensor detects motion to verify detection is
active.
• Beep warn - unit beeps 3 times after delayed-OFF time
Lighting status Ambient Light Room vacant, delayed-OFF Room vacant, delayed-OFF
during occupancy. Override time expires. time expires.
NOTE: Previous Lighting status when personnel Lighting status when personnel
status does not re-enter darkened room re-enter room with ample
in Class Room Mode natural lighting
1 Not applicable Not Set Primary: ON Primary: ON
Secondary: ON Secondary: ON
2* Not applicable Set Primary: ON Primary: ON
Secondary: ON Secondary: OFF (Secondary responds
to light override
OPERATION IN CONFERENCE ROOM MODE (ODS0D-ID)
Lighting status Ambient Light Room vacant, delayed-OFF Room vacant, delayed-OFF
during occupancy Override time expires. time expires.
Lighting status when personnel Lighting status when personnel
re-enter darkened room re-enter room with ample
natural lighting
1 Primary: ON Not Set Primary: ON Primary: ON
Secondary: ON Secondary: ON Secondary: ON
2 Primary: ON Set Primary: ON Primary and Secondary remain OFF
Secondary: ON Secondary: ON due to light override
3 Primary: ON Not Set Primary: ON Primary: ON
Secondary: OFF Secondary: OFF Secondary: OFF
4 Primary: ON Set Primary: ON Primary and Secondary remain OFF
Secondary: OFF Secondary: OFF due to light override
5 Primary: OFF Not Set Primary: OFF Primary: OFF
Secondary: ON Secondary: ON Secondary: ON
6 Primary: OFF Set Primary: OFF Primary and Secondary remain OFF
Secondary: ON Secondary: ON due to light override
7 Both Primary and Not Set Primary: ON Primary: ON
Secondary turned Secondary: OFF Secondary: OFF
OFF for viewing
mode
8 Both Primary and Set Primary: ON Primary and Secondary remain OFF
Secondary turned Secondary: OFF due to light override
OFF for viewing mode
OPERATION IN CLASSROOM MODE (ODS0D-ID)
*Example Number 2, with the Ambient Light Override set, is more typical of the Classroom Mode.
expires, then waits 10 seconds before turning lights OFF.
• One unit can be used for 120V through 277V lighting.
Compatible with both electronic and magnetic ballasts.
• Primary relay switches at the zero crossing point of the
AC power curve to ensure longer contact life and com-
patibility with electronic ballasts.
Unit fits in standard single-gang wallbox and replaces
two
single-pole wall switches; ground connection required.
Gangable with other devices.
• Exclusive Leviton H.I.S. Circuitry. Specifically designed to
handle today’s high inrush electronic ballast loads and
offer unmatched durability and service.