Specification
PRODUCT DATA
ODS0D
ing tape required.
• Time delay adjustment for delayed-OFF time settings of
30 seconds, 5, 10, and 30 minutes. Allows customized
adjustments to maximize energy savings.
• Vandal resistant PIR lens.
• False detection circuitry.
• Light Sensor adjustable Ambient Light Override ranges
from approximately 2FC (20 LUX) to 500+FC (5000+ LUX).
• Manual-ON/auto-OFF mode for installations where manual-
ON switching is required but auto-OFF switching is still
desired for CEC Title T24 energy savings.
• To comply with CEC Title 24, red LED indicator light flashes
when PIR sensor detects motion to verify detection is
active.
• Beep warn - unit beeps 3 times after delayed-OFF time
Lighting status Ambient Light Room vacant, delayed-OFF Room vacant, delayed-OFF
during occupancy. Override time expires. time expires.
NOTE: Previous Lighting status when personnel Lighting status when personnel
status does not re-enter darkened room re-enter room with ample
in Class Room Mode natural lighting
1 Not applicable Not Set Primary: ON Primary: ON
Secondary: ON Secondary: ON
2* Not applicable Set Primary: ON Primary: ON
Secondary: ON Secondary: OFF (Secondary responds
to light override
OPERATION IN CONFERENCE ROOM MODE (ODS0D-ID)
Lighting status Ambient Light Room vacant, delayed-OFF Room vacant, delayed-OFF
during occupancy Override time expires. time expires.
Lighting status when personnel Lighting status when personnel
re-enter darkened room re-enter room with ample
natural lighting
1 Primary: ON Not Set Primary: ON Primary: ON
Secondary: ON Secondary: ON Secondary: ON
2 Primary: ON Set Primary: ON Primary and Secondary remain OFF
Secondary: ON Secondary: ON due to light override
3 Primary: ON Not Set Primary: ON Primary: ON
Secondary: OFF Secondary: OFF Secondary: OFF
4 Primary: ON Set Primary: ON Primary and Secondary remain OFF
Secondary: OFF Secondary: OFF due to light override
5 Primary: OFF Not Set Primary: OFF Primary: OFF
Secondary: ON Secondary: ON Secondary: ON
6 Primary: OFF Set Primary: OFF Primary and Secondary remain OFF
Secondary: ON Secondary: ON due to light override
7 Both Primary and Not Set Primary: ON Primary: ON
Secondary turned Secondary: OFF Secondary: OFF
OFF for viewing
mode
8 Both Primary and Set Primary: ON Primary and Secondary remain OFF
Secondary turned Secondary: OFF due to light override
OFF for viewing mode
OPERATION IN CLASSROOM MODE (ODS0D-ID)
*Example Number 2, with the Ambient Light Override set, is more typical of the Classroom Mode.
expires, then waits 10 seconds before turning lights OFF.
• One unit can be used for 120V through 277V lighting.
Compatible with both electronic and magnetic ballasts.
• Primary relay switches at the zero crossing point of the
AC power curve to ensure longer contact life and com-
patibility with electronic ballasts.
• Unit fits in standard single-gang wallbox and replaces
two
single-pole wall switches; ground connection required.
Gangable with other devices.
• Exclusive Leviton H.I.S. Circuitry. Specifically designed to
handle today’s high inrush electronic ballast loads and
offer unmatched durability and service.