ODS0D
INSTALLATION
The ODS0D is designed to control two separate light-
ing loads for bi-level or A/B switching (inner and outer
banks of fluorescent lighting or separate banks of
incandescent lighting) in the area it is monitoring. The
light sensor Ambient Light Override is an important
energy-saving, daylight harvesting feature that also
distinguishes the functioning of the Conference Room
and Classroom modes (see “Operation Modes”). The
Ambient Light Override should always be adjusted
during the time of day when the ambient light is at a
level where no additional lighting is required. Exclusive
auto-adapting operating features will automatically
compensate for real-time occupancy patterns to pro-
vide maximum convenience and energy savings.
The ODS0D mounts in a standard single-gang wallbox
and will replace two single-pole wall switches that
control two separate lighting loads. The unit must
be properly grounded in order to operate. The unit’s
patented integral blinders may be used to restrict the
field of view to prevent unwanted detection of hallway
traffic. No masking tape required.
The ODS0D should be positioned at least 6 feet away
from HVAC registers. The switch located under the
push-button provides three operational settings: “ON”
turns the lighting load ON indefinitely (motion detec-
tion not active), “OFF” disconnects the lighting load
from the power for relamping purposes, and “AUTO”
activates automatic motion detection. Note that
whenever the unit is powered up, it will take approxi-
mately 1 minute to begin normal operation.
Hot (Black)
Phase 1
Neutra l (White)
ODS0D
Black
Green
Ground
Blue
Red
Red
Line
120-230-277VAC,
60H z
Primary
Load
Secondary
Load
Note: Ground must be connected
WIRING DIAGRAMS
ODS0D-ID Wiring Diagram for Single Pole Application—Single Phase
Hot (Black)
Phase 1
Neutra l (White)
ODS0D
Black
Green
Ground
Blue
Red
Red
Line
120-230-277VAC,
60H z
Primary
Load
Secondary
Load
Note: Ground must be connected
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Black
Green
Ground
Blue
Red
Red (To Phase 2)
Line
120-230-277VAC,
50/60Hz
ODS0D
ODS0D-ID Wiring Diagram for Single Pole Application—2 Phase
Hot (Black)
Phase 1
Neutra l (White)
ODS0D
Black
Green
Ground
Blue
Red
Red
Line
120-230-277VAC,
60H z
Primary
Load
Secondary
Load
Note: Ground must be connected
3
FIELD-OF-VIEW
The ODS0D provides a 180° field-of-view with a maxi-
mum coverage area of approximately 2100 square
feet. The maximum sensing distance in front of the
sensor is 40 feet, and at each side is 30 feet. The
“minor motion” zone detects relatively small body
movements and allows the lights to stay ON even
though a person may not be moving or walking around
the room. The remainder of the field-of-view, the
“major motion” zone, exhibits a lesser degree of sensi-
tivity and requires larger movements.
ODS0D-ID/-TD
Field-of-View (in feet)
TO P VIEW
SIDE VIEW
ODSXX-ID
15 40
0
0
15
15
30
30
40
40
4
Minor Motion, IR
Major Motion, IR
5
0
TO P VIEW
SIDE VIEW
ODSXX-ID
15 40
0
0
15
15
30
30
40
40
4
Minor Motion, IR
Major Motion, IR
5
0