Product Overview

Leviton Manufacturing Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062•Tel:1-800-736-6682•FAX:503-404-5594•TechLine(6 AM - 4 PM Mon-Fri): 1-800-959-6004
Leviton Manufacturing Co., Inc. Global Headquarters
201 N. Service Rd., Melville, NY 11747-3138•TechLine:1-800-824-3005•FAX:1-800-832-9538
Leviton Manufacturing of Canada, Ltd.
165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9•Telephone:1-800-469-7890•FAX:1-800-563-1853
Leviton S. de R.L. de C.V.
Lago Tana 43, Mexico DF, Mexico CP 11290•Tel.(+52) 55-5082-1040•FAX:(+52) 5386-1797•www.leviton.com.mx
Visit our Website at: www.leviton.com/les
© 2014 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
G-9008B/E14-aa
REV MAY 2014
PRODUCT DATA
OPP20-0D1 OPP20-0D2 OPP20-RD3 OPP20-RD4
ORDERING INFORMATION*
DESCRIPTION CAT. NO. POWER INPUT RELAY RATING
CONTROL
INPUTS
POWER
SUPPLY
OUTPUT
Power Pack, Basic
with Auto-ON
OPP20-0D1
120-230-277VAC,
50/60 Hz
20A, 2400W @ 120V Resistive
20A, 2400W @ 120V General Purpose
20A, 2400W @ 120V Incandescent
20A, 2400W @ 120V – Fluorescent
20A, 5540W @ 277V – Resistive
20A, 5540W @ 277V – General Purpose
20A, 5540VA @ 277V – Fluorescent
16A, 4430VA @ 277V – Electronic Ballasts
1/2 HP @ 120V – Motor Load
2 HP @ 240/277V – Motor Load
Suitable for general purpose plug load
control - 20A, 2400W @ 120V
- complies with ASHRAE 90.1 and CA Title
24 Plug Load Control Requirements
2mA, 24VDC
225mA,
24VDC, 5.4W
Power Pack with
Auto-ON,
Manual-ON, and
Local Switch
Inputs, Title 24
OPP20-0D2
Power Pack with
Auto-ON and
Photocell Input
OPP20-RD3
Power Pack with
Auto-ON,
Manual-ON,
Local Switch, and
Photocell Input,
Title 24
OPP20-RD4
DESCRIPTION CURRENT CONSUMPTION
OSC04-I, OSC15-I, OSWHB-I, OSWLR-I, OSWWV-I 10-15mA
OSC05-M, OSC05-U, OSW12-M 25mA
OSC10-M, OSC10-U 35mA
OSC20-M, OSC20-U 30mA
OSA20-R Add-a-Relay 50mA
ODC0P-S0W Switching Photocell 10mA
POWER PACK CAPACITY FORMULA
Leviton power packs can be used to provide power to one or more occupancy sensors. Since current consumptions of occupancy
sensors may vary, the best way to ensure you order the correct number of power packs and add-a-relays is by using this formula:
# of sensor # of sensor # of Add a
Model As Model Bs Relays
X + X + X
Sensor A current Sensor B current 50mA
consumption consumption
SPECIFICATIONS
ENVIRONMENTAL
Operating Temperature Range 32°F to 122°F (0°C to 50°C)
Relative Humidity 0% to 90% non-condensing, for indoor use only
OTHER
Construction Case: high impact, UL rated plastic
Relay: 60A rated magnetic latching relay; silver alloy contacts
Wire: 6” leads, 18AWG input; 14AWG load; LV connections: 8” leads 22AWG
Dimensions 2.400”H x 3.811”W x 1.432”D (60.96mm x 96.80mm x 36.37mm)
Listings UL/cUL Listed, FCC Certified, NOM Certified, CA Title 24 Compliant, meets ASHRAE 90.1
requirements, RoHs Compliant
Color Gray
Warranty Limited Five-Year Warranty
*For CE Compliant Lighting Control Module, see the OPPCE data sheet.
Power supply output per
below chart
< 225mA