Instructions / Assembly

Ultrasonic Ceiling Mounted Occupancy Sensor
Cat. No. OSC
Ø
5-U, OSC1
Ø
-U, OSC2
Ø
-U
To be used with 24VDC OSPxx Series and CN100 Power Pack Class II Low-Voltage Wiring
INSTALLATION INSTRUCTIONS
Tools needed to install your Sensor
Slotted/Phillips Screwdriver Electrical Tape
Pliers Pencil
Cutters
Parts Included List
Sensor (1) #8-32 Washer and Nut (2)
#8-32 x 1/2" Screw (2) Threaded Rod (1) and Hex Nut (1)
#8-32 x 1-1/2" Screw (2) Plastic Washer (1)
DESCRIPTION
The Occupancy Sensor is a low-voltage ultrasonic sensor that works with the OSPxx
Series and CN100 power pack to automatically control lighting. The sensor turns the
lights on and keeps them on whenever occupancy is detected and will turn them off
after the ‘delayed-off time’ has expired.
The sensor continually analyzes and adjusts to changing conditions. The sensor uses
the latest microprocessor-based technology which permits it to continually adjust and
optimize its performance.
Ultrasonic (doppler shift) motion detection gives maximum sensitivity that yields a
sensor with excellent performance.
INSTALLING YOUR OCCUPANCY SENSOR
NOTE: Use check boxes when Steps are completed.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF
POWER at circuit breaker or fuse and test that power is off before wiring!
Step 1
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&/./&&
/./&&
/./&&
/./&&
/./&&
Step 3 cont'd
5. Push the wires into the hole in the ceiling tile and insert the threaded rod until the
sensor is flush with the tile.
6. Insert wires through the hole in the included washer, then place the included washer
over the rod and screw on the included hex nut.
7. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per WIRING
DIAGRAM as follows: Twist strands of each lead tightly and, with circuit conductors,
push firmly into appropriate wire connector. Screw connectors on clockwise making
sure that no bare conductor shows below the wire connectors. Secure each connector
with electrical tape.
8. Rotate the sensor to the desired orientation. Note that the sensor base and back cover
are keyed. To lock the device in place, ensure that the arrows are not aligned.
9. Restore power at circuit breaker or fuse to Power Pack.
INSTALLATION IS COMPLETE.
Low-Voltage Wires
Low-Voltage Wires
Sensor Back
Cover
Sensor Base
Keylock Arrow
Mounting Screws
(2 places)
Sensor Front Cover
Wallboard Ceiling
Back Cover open center to
route Low-Voltage Wires
Mounting Screw
Back Cover internal
surface shown
Back Cover shown mounted
on ceiling with screws
Nut (2 places)
Washer (2 places)
Wallboard
Ceiling
#8-32 Screws
(2 places)
O
ctagon
B
ox
4" x 1-1/2" deep
Low-Voltage
Wires
Wallboard or
Drop Ceiling
Wire Mold Back Cover
Back Cover Screws
(4 places)
Wire Mold Round Fixture
Box Cat. No. V5738
(for raceway mount)
Mounting Screws
(4 places)
Low-V
oltage Wires
Wallboard Ceiling
Wire Mold Raceway
(use applicable fittings)
Hot (Black)
Neutral (White)
Load
Blue
(Control)
Black
Red (24VCD)
Red
Blue
White
Black
White
Black
Red
Gray
*
Blue
Blue
Blue
Black
Black
Line
120/277/347 VAC
60Hz
Sensor
OSPxx Series
Power Pack
NC - Brown
NO-Brown/White
Common-Green
To HVAC
System
Gray*
Occupancy Sensor Mounted to Octagon
Box Installed Flush to Wallboard Ceiling
Occupancy Sensor Mounted to Round Fixture
with Raceway for Wallboard Installation
Wiring Diagram: Multiple Sensor, Single Power Pack
*NOTE: When using the
Photocell function, connect
the Gray wire of the sensor
to the Blue wire of the
power pack. DO NOT use
the Blue wire of sensor.
NOTE: Ensure to cap wire
that is not being used.
Low-Voltage Wires
NOTE: Wires routed through
Threaded Rod
Drop Ceiling
1" thick maximum
Nut
Washer
Threaded Rod
Mounting Option Diagram A
Occupancy Sensor Mounted to Drop Ceiling Using Threaded Rod
Mounting Option Diagram B
Occupancy Sensor Mounted to Wallboard or Drop Ceiling Using Screws
PK-93585-10-00-0F
1-Way
Ultrasonic
2-Way
Ultrasonic
2-Way
Ultrasonic
Description
Mount in corner/
over doorway
Mount in center
of room/area
Mount in center
of room/area
Suggested
Mounting Location
40 KHz
40 KHz
32 KHz
Operating
Frequency
30mA
40mA
32mA
Current
Consumption
OSC05-U0W
OSC10-U0W
OSC20-U0W
Cat. No.
CATALOG ITEMS
500 sq. ft.
Coverage
2000 sq. ft.
1000 sq. ft.
Preparing and Connecting Wires:
1/2"
(1.3 cm)
Strip Gage
(measure bare
wire here)
Cut
(if necessary)
Step 2
Typical Installations:
Listed are 3 typical installation options (A, B, and C). Choose one that
best suits your needs. Other methods of installation may be possible but
they have not been described here.
A. Drop Ceiling Installation (Mounting Option A):
NOTE: Use the threaded rod included.
1. Select location for mounting of sensor for your application (refer to Mounting
Location Diagram).
2. Use the supplied threaded rod or other methods to make a hole (1/2" to 1") in the
ceiling tile just large enough to pass the body of the threaded rod through.
3. Insert the sensor wires through the flared end of the threaded rod. Position the
threaded rod to the base of the sensor.
4. Insert the flared end of the threaded rod into the opening in the bottom of the sensor
and twist to lock into place.
Step 3
Step 3 cont'd Step 3 cont'd
C. Junction Box or Surface Mount Raceway Installation (refer to
Mounting Diagrams):
NOTE: Listed below are suggested JUNCTION BOX installation applications which
require mounting to conduit in one of the following three ways:
B. Wallboard or Drop Ceiling Installation (Mounting Option B):
NOTE: You may use the mounting screws, nuts and washers included, or screws in
combination with commercially available wall anchors.
1. Select location for mounting of sensor for your application (refer to Mounting
Location Diagram).
2. Make a hole in the ceiling tile or wallboard large enough to pass the wire connections
and wire nuts through (approximately 1" diameter).
3. Remove the back cover of the sensor. Hold the back cover and body of the sensor and
rotate until the two arrows line up and pull apart.
4. Install back cover of the ceiling sensor to the wallboard or drop ceiling using the
included screws, nuts and washers, or screws in combination with commercially
available wall anchors.
5. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per WIRING
DIAGRAM as follows: Twist strands of each lead tightly and, with circuit conductors,
push firmly into appropriate wire connector. Screw connectors on clockwise making
sure that no bare conductor shows below the wire connectors. Secure each connector
with electrical tape.
6. Push wire connections through the center hole of the back cover and into the ceiling.
7. Secure the sensor body to the back cover by aligning the arrows. Lock it by turning the
sensor such that the arrows do not line up.
8. Rotate the sensor to the desired orientation.
9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS
COMPLETE.
TABLE 2: WIRE DESIGNATIONS
Name
Power (+24 V)
DC Return
Occupancy
Occupancy/Photocell
Color
Red
Black
Blue
Gray
Gage
24
24
24
24
Temp/Voltage
200° C/ 600V
200° C/ 600V
200° C/ 600V
200° C/ 600V
FCC COMPLIANCE STATEMENT:
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions:
(1) This device must not cause harmful interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
WARNINGS AND CAUTIONS
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
Sensors must be mounted on a vibration free surface.
All sensors must be mounted at least 6 feet away from air vents.
Do not touch the surface of the lens. Clean outer surface with a damp cloth only.