Specification

PRODUCT DATA
Fixture Mount PIR High Bay/Low Bay
Dimming Occupancy Sensor
With Integrated Photocell and Two Interchangeable Lenses
HB011
BASIC OPERATION
The HB011 PIR Fixture Mount High Bay/Low Bay
Dimming Occupancy Sensor with Integrated Photocell
and Two Interchangeable Lenses provides 1-10V
control. The HB011 is easy to program and set for
desired 1-100% continuous dimming levels during
daylighting. It is also engineered to meet and exceed
all standards requirements of ASHRAE Standard 90.1
2016.
Whether factory or field installed, new installation or
retrofit, Leviton fixture mounted sensors provide fast,
easy installation and immediate energy savings by
automatically activating lighting only during periods
of occupancy. The innovative, integrated design
includes a built-in photocell for simplified installation
and convenient automatic daylighting. Reliable
passive infrared (PIR) technology detects occupancy,
and the variable time delay (up to 30 minutes) is user
accessible without power, tools or disassembly, and
allows the ideal setting based on application needs.
Included with the sensor are lenses for high-bay and
low-bay applications, allowing one unit to cover a
variety of high ceiling applications. The innovative
Autocal™ feature performs an automatic daylight
level calibration. Once calibrated, the sensor requires
no further adjustment and immediately enters
daylight harvesting mode, actively dimming the
connected fixture load in response to occupancy and
available natural light, maximizing energy savings
through efficient daylighting.
APPLICATIONS
• Warehouses
• Manufacturing
• Indoor parking garages
INSTALLATION
The HB011 installs directly to an industrial fluorescent
fixture or an electrical junction box through a
standard 1/2” knockout using the provided lock-
nut. Wiring is connected inside the fixture body. The
sensor is installed in one of three 1/2” punch-outs,
positioning the HB011 at the correct field-of-view
position flush or below the fixture reflector assembly.
FEATURES
• 1-100% continuous dimming control
• Specifically designed for LED fixture control
• Patented AutoCal™ for set-it and forget-it photocell
calibration
• Suitable for use in standard and cold storage
applications
• Visual RGB LED indicators for device states and easy
troubleshooting
• Alternating relay software for increased lamp life
• Interchangeable 360° high bay and low bay lenses
included
• Adjustable time delay (no power required)
• Pre-stripped color-coded wire leads
• Quicksnap feature for easy installation
• H.I.S. (High Inrush Stability) Technology
- Zero crossing circuitry
- Robust mechanical latching relay
• Relay always returns to close after power loss event
• UL listed for electronic ballast loads 120/277V
Leviton Manufacturing Co., Inc. Global Headquarters
201 North Service Road, Melville, NY 11747-3138 tech line 800-824-3005 fax 800-832-9538
©2017 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.