Installation Guide

Fixed Time Delay:ThexedTime-Outvalueisselectedbyrotatingthe
TimeControldial.Therearefour(4)valuesfromwhichtochoose.Each
markaroundthedialcorrespondstoadifferentvalueasindicatedbelow
(refer to Control Panel Diagram).
NOTE:Alltimedurationsareapproximatewithin±10seconds.
Adapting Time Delay:TheSensorhasbuiltinadaptingintelligencethat
changestheAdaptingTime-Outdurationinresponsetotheoccupancy
conditionsoftheroomitisinstalledin.IftheSensordetects“large,”
infrequentmotionitwillINCREASEtheAdaptingTime-Outduration.If
theSensordetects“large,”frequentmotion(asinseveralpersonsina
roomduringameeting),itwillDECREASEthetime-outdurationonly
ifitwasNEVERincreased(thisisbecausethebuiltinintelligencewill
alwaysproceedinthedirectionof“increasing”adaptingTime-Outonce
ithasincreaseditforanyoftheoccupancyconditionssensed).The
AdaptingTime-Outdurationwillrangefrom10to30minutesintimeplus
theWalk-ThroughTimeDelay.
Walk-Through Time Delay:Thewalk-throughfeaturewhichisonly
activeintheAdaptingTime-Outmode,isusefulwhenaroomis
momentarilyoccupied.Withthisfeature,theSensorwillturnthelights
OFFshortlyafterthepersonleavestheroom.Thewalk-throughfeature
worksinthefollowingmanner:Whenapersonenterstheroom,the
lightswillturnON.Ifthepersonleavestheroombeforethewalk-through
time-outof2.5minutes,theSensorwillturnthelightsOFFafter2.5
minutes.Ifthepersonstaysintheroomforlongerthan2.5minutes,the
SensorwillinsteadusethestoredAdaptingTime-OutDelaysetting.
IftheSensordetectsmotionwithin30secondsafterthelightsturnOFF,
itwillturnthelightsONandincreasethetime-outvalueby1.5timesthe
existingvalue.
TheAdaptingTime-Outmayberesettothebasevalueof30minutesby
rotatingtheTimeControltoanewtimeselectionvalueandthenbackto
theAdaptingTime-Outvalue(refer to Control Panel Diagram).
Ambient Light Override:TheAmbientLightOverrideisusedtokeep
thelightsOFFifthereisalreadyenoughnaturallightintheroom.
Forproperoperation,theAmbientLightOverrideadjustmentmustbe
performedwhenthereisenoughnaturallight(refer to the SETTINGS
section).Iftheadjustmentismadewhenthereislessnaturallight,the
lightsmaynotturnONeventhoughtheyareneededandwillrequire
manualactivationofthepush-buttonstoturnthelightsON.
NOTE:Theambientlightlevelinthecenterofaroomwillbedifferent
thanthelevelatthewallwheretheswitchislocated.
Ambient Light Dial:Theambientlightsettingisadjustedwiththe
AmbientLightDial(refer to Control Panel Diagram).TurningtheLight
Dialfullycounter-clockwise(CCW),setstheSensortomanualONmode
(seefollowingsection).IfthelightcontrolisinthefullyCWposition,the
lightswillturnONwhenevermotionisdetected,eveninfulldaylight.
IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
NOTE:WhenthesettingisattheminimumCCWlevel,thelightswill
stayOFFwhentheroomisdim.Whenthesettingisatthemaximum
levelclockwise(CW),thelightswillturnONwhentheroomisbright.
Manual ON Mode:WhenthelightcontrolisinthefullyCCWposition
thelightswillneverautomaticallyturnON.Inthismodethelightsneed
tobemanuallyturnedONbythepush-button,andwillturnOFFwiththe
absenceofmotion.
PIR RANGE:TodecreasePIRdetectionrangeandsensitivity,rotatethe
knobCCW(refer to Control Panel Diagram).Thedetectionrangecan
beadjustedfrom100%downto30%.
ULTRASOUND (US) SENSITIVIY AND PIR DISABLE:USsensitivity
canbeadjustedtoHIGH-MEDIUMorLOWbyholdingtheONbutton
for15seconds.TheLEDwillashtorepresenttheUltrasonicsensitivity
andPIRstatus.TappingtheONbuttonduringthedesiredLEDash
indicationwillsettheUltrasonicsensitivityandPIRstatus.Usethe
followingchart:
Note:Todisable/enableUltrasonicTechnology:
1 Turnthe"light"adjustmentknobCCW.
2 Holdthebuttondownfor6-7seconds.
3 Relasebutton.RedLedblinking=PIRonly.
GreenLEDblinking=USactive.
TIME
1
2
A
3
RANGE
BLINDERS
LIGHT
4
7
10
4
7
10
Slash Mark
Blinder adjustment levers
Control Panel Cover
PUSH BUTTON(S)
Cat.No.OSSMT-GDxhasasinglepush-buttonswitchthattogglesthe
relayanditscorrespondingload,ONandOFF(refertogure).Ifthe
relayisOFF,therelaywillturnONwhenthepush-buttonispressed,
andremainONinthepresenceofmotion.Intheabsenceofmotion,the
SensorUnitwillTime-OutandturntherelayOFF.
NOTES:
• TheMotionIndicatorLEDwillblinkeverysecondwhilemotion
isdetected.AredblinkrepresentsPIRdetection,agreenblink
representsUltrasonicdetection.
• WhentheTime-OutexpiresandtherelayturnsOFFa30second
vacancyconrmationexisttoturntherelaybackON.Afterthistime
thedevicewillbeplacedintoalowerdetectionthresholdmode.
• InManual-ONmode,thebuttonmustbepressedtoturnthelightsON.
Intheabsenceofmotion,theunitwillTime-OutandturnthelightsOFF.
• IfManual-Onmodeisdesired,keeptheLightknobinthefully
counter-clockwise(CCW)position.
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becarefulNOT
TOOVERTURNoruseexcessiveforcewhensettingthecontrol
knobsorleversofCatNo.OSSMT.Useasmallstraightblade
screwdrivertoadjusttheknobsandyourngertoadjusttheblinder
levers.
1. RemoveDecora
®
wallplateandControlPanelCoverfromSensor.
2. RotatetheTimedialtoselectthedesiredxedTime-Outvalue.
3. IftheSensorisinstalledwithin6feetofanairduct,rotatetheRange
Control1/4turncounter-clock-wise(CCW).
4. Set the Ambient Light Level - AMBIENT LIGHT:Cat.No.OSSMT
hasanadjustmenttodetermineatwhatminimumambientlight
leveltheunitwilloperate.Theadjustmentshouldbemadewhenthe
ambientlightisatthelevelwherenoarticiallightisneeded.Follow
thesestepstomakeamoreaccurateadjustmentofthelightcontrol.
ThisfeaturewillnotworkinManual-Onmode.
A. WiththelightsON,rotatetheTimeControlfullyCCWtotheset
theTime-Outtothethirty(30)secondtestmode(refer to Control
Panel Diagram).
B. RotatetheLightControlfullyCCW.
C. ManuallyturnOFFthelights.
D.
RotatetheLightControlclockwise(CW)SLOWLY,untilthelights
turnON.Thisisthesettingforthecurrentleveloflightintheroom.
Adjustthelightcontrolback(CCW)alittlesothelightswillnotturn
onwiththecurrentroomlightinglevel.Leavetheroomandwait
forthe30-secondtimeoutand30-secondvacancyconrmation
(45-secondconrmationfortheOSSMT-MD)toexpire.Performa
walkthroughtoseeifthelightsturnonwiththenewambientlight
leveladjustment.Repeatthisadjustmentasneededtokeepthe
lightsfromturningonunderconditionswhenenoughlightispresent.
NOTE:WhenthelightcontrolisinthefullyCCWpositionthelights
willneverautomaticallyturnON.ThisistheManual-Onmode,
wherethelightsneedtobemanuallyturnedONbythe
push-button,andwillturnOFFwiththeabsenceofmotion.
IfthelightcontrolisinthefullyCWposition,thelightswillturnON
whenevermotionisdetected,eveninfulldaylight.
IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
NOTE:Theambientlightinaroomwillchangewiththetimeofday
andtheseasonoftheyear.
5. Time-Out Settings:
A. AdjusttheTimedial.TheSensorAmberLEDwillashtwiceeach
timetheTimedialispointedatanewTime-Outvalue.
TheTime-Outvaluesfornon-adaptingmodeare:
NOTE:Toreturntoadaptingmode,rotatetheTimedialtofullCW
position(Asetting).BesuretheTimedialisrotateduntilanAmber
LEDashisissuedtobesureanewsettingwasselected.
(/)SlashMark
1
2
3
A
30secondxedtime-outforperformingawalktest
10minutesxedtime-out
20minutesxedtime-out
30minutesxedtime-out
AutoAdapting
Value of TimeFace Marking
SETTINGS
OPERATION
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenetofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforveyearsfromthepurchasedate.Leviton’sonlyobligationistocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchveyearperiodtheproductisreturnedprepaid,
withproofofpurchasedate,andadescriptionoftheproblemtoLeviton Manufacturing Co., Inc., Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,
overloaded,misused,opened,abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.Therearenootherorimpliedwarrantiesofanykind,includingmerchantabilityandtnessforaparticularpurpose,butifanyimpliedwarrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,
includingmerchantabilityandtnessforaparticularpurpose,islimitedtoveyears.Levitonisnotliableforincidental,indirect,special,orconsequentialdamages,includingwithoutlimitation,damageto,orlossofuseof,anyequipment,lostsalesorprotsordelayorfailuretoperformthiswarrantyobligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,
whetherbasedoncontract,tortorotherwise.
1. IfthereisnoresponsefromtheunitandtheLEDneverblinksorthe
pushbuttondoesnotactivatethelights1-1/2minutesafterpoweris
applied,thenuninstalldeviceandverifywiring(Step 4).
2. IfthelightsconstantlystayON,evenwhentheroomisunoccupied:
A.ChecktheTimesetting.Seehowthistimecomparestohowlong
thelightsstayON.
B.TryloweringthePIRRangeControl.Rotatetheknob
counterclockwiseabout30°.
C.Iftheproblempersists,tryreducingagain.
NOTE:DonotreducesomuchthattheSensorUnitcannotsee
normaloccupancy.
D.TryloweringtheUltrasonicSensitivity.
E.BesuretousetheBlinderstoblockanyunwantedhallwaytrafc.
F. Checkforreectedheat/motionastheSensorUnitmaybeseeing
motionthroughawindow.
G.CheckforadjacentHVACand/orheaterducts.
H.IfyourOSSMT-GDdoesnotseemtobefunctioningandhasa
ashingamberLED,theremaybeazero-crossfailure.Pleasecall
fortechnicalassistance.
IfyourOSSMT-MDhasaashingamberLED,thezero-cross
failureover-ridehasoccured,butthesensorwillstilloperateuntil
youareabletoreachtechnicalassistance.
TROUBLESHOOTING
Lens
Blinders
Control panel
cover
Push button
LED window
US sensor ports
• Fortechnicalassistancecontactusat1-800-824-3005
• Visitourwebsiteatwww.leviton.com
PRODUCT INFORMATION
• Securedevicebyrmlytighteningmountingscrews.
• InstallDecora
®
stylewallplate(soldseparately).
Small Motion=DualTechnologycoverage.Thisalsorepresentsthe
maximumultrasonicrangecoverage.
Wall surface
Device mounting screw
(2 places)
Wallplate
Wallplate
mounting
screw
(2 places)
20 ft (6.1 m)
small motion
30 ft (9.1 m)
20 ft (6.1 m)
small motion
40 ft
(12.2 m)
Field - of - View (Horizontal)
40 ft.
(12.2 m)
4 ft.
(1.2 m)
Sensor
Side (Vertical) Field - of - View
DI-0XX-OSSMT-00B
©2010LevitonMfg.Co.,Inc.
Control Panel Diagram
US Sensitivity and PIR Disable
3 amber flashes High ultrasonic sensitivity, PIR enabled
2 amber flashes Medium ultrasonic sensitivity, PIR enabled
1 amber flash Low ultrasonic sensitivity, PIR enabled
3 green flashes High ultrasonic sensitivity, PIR disabled
2 green flashes Medium ultrasonic sensitivity, PIR disabled
1 green flash Low ultrasonic sensitivity, PIR disabled
NOTE:Theprogramtimesoutin30secondsfromthelastbutton
press.ThefactorysettingfortheUSsensitivityisMediumwithPIR
andUltrasonictechnologiesenabled.
7. ReplacetheControlPanelCoverandDecora
®
wallplate.
6. Ifdesired,adjusttheblinderstoblockanyunwantedmotion.
FCC COMPLIANCE STATEMENT
ThisdevicecomplieswithPart15oftheFCCRules.Operationissubjecttofollowing
twoconditions:(1)thisdevicemaynotcauseharmfulinterference,and(2)this
devicemustacceptanyinterferencereceived,includinginterferencethatmaycause
undesiredoperationofthedevice.
ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassB
DigitalDevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesigned
toprovidereasonableprotectionagainstharmfulinterferenceinaresidential
installation.Thisequipmentgenerates,uses,andcanradiateradiofrequency
energyand,ifnotinstalledandusedinaccordancewiththeinstructions,maycause
harmfulinterferencetoradiocommunications.However,thereisnoguaranteethat
interferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescause
harmfulinterferencetoradioortelevisionreception,whichcanbedeterminedby
turningtheequipmentOFFandON,theuserisencouragedtotrytocorrectthe
interferencebyoneormoreofthefollowingmeasures:
• ReorientorrelocatethereceivingAntenna.
• Increasetheseparationbetweentheequipmentandthereceiver.
• Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthe
receiverisconnected.
• Consultthedealeroranexperiencedradio/tvtechnicianforhelp.
FCC CAUTION
AnychangesormodicationsnotexpresslyapprovedbyLevitonManufacturingCo.,
Inc.,couldvoidtheuser'sauthoritytooperatetheequipment.