Specification

PRODUCT DATA
OSSNL
FEATURES CONT.
• To  comply  with  T24,  red  LED  indicator  light  flashes 
when sensor detects motion to verify detection is
active.
•  Time  Delay  adjustment  for  delayed-OFF  time  set-
tings of 30 seconds (for walking test), 10 minutes, 20
minutes, and 30 minutes. Allows customized adjust-
ments to maximize energy savings.
Light Sensor Adjustable Ambient Light Override
ranges from approximately 2 foot-candles (20 lux) to 
500+ foot-candles (5000+ lux) to prevent lights from 
turning ON automatically during periods of ample
natural light, increasing energy savings.
• Light sensor enables the load hold-OFF feature once 
level has been set.
• Vacancy confirmation - when the time out expires and 
the relays turn OFF, a 30 second vacancy confirmation
exists to turn the relays back ON.
• False detection circuitry.
• Presentation Mode feature for slide or film presenta-
tions allows push buttons to turn lights OFF and keep
them OFF while the room is occupied.
• LED NightLight offers “Guide Light” functionality.
• Adjustable NightLight illumination setting for continu-
ous or dimmed NightLight.
• NightLight Mode - the factory default setting for the 
NightLight Mode is Dimmed Mode. This means the
NightLight will automatically dim to 5% of full bright-
ness after 2 minutes of no occupancy when activated
by the internal light sensor.
• One unit can be used for 120V through 277V lighting. 
Compatible  with  both  electronic  and  magnetic  bal-
lasts.
• Relay  switches  at  the  zero  crossing  point  of  the  AC 
power  curve  to  ensure  maximum  contact  life  and 
compatibility with electronic ballasts.
• Exclusive Levition H.I.S. Circuitry. Specifically designed 
to handle today’s high inrush electronic ballast loads
and offer unmatched durability and service.
OSSNL
Field-of-View (in feet)
TO P VIEW
SIDE VIEW
ODSXX-ID
15 40
0
0
15
15
30
30
40
40
4
Minor Motion, IR
Major Motion, IR
5
0
FIELD OF VIEW
The OSSNL provides a 180° field of view with a maxi-
mum  coverage  area  of  approximately  2100  square 
feet.  The  maximum  sensing  distance  in  front  of 
the sensor is 40 feet, and at each side is 30 feet. A 
“minor-motion”  zone  detects  relatively  small  body 
movements and allows the lights to stay ON even
though a person may not be moving or walking
around the room. The remainder of the field of view,
the “major-motion” zone, exhibits a lesser degree of 
sensitivity and requires larger movements.
INSTALLATION
The OSSNL is preset to deliver optimum performance
in a wide variety of applications without requiring any
adjustments during installation. The unit may replace
a single-pole wall switch mounted in a standard
wall box. The unit must have a neutral and be prop-
erly grounded in order to operate. The unit’s integral
blinders may be used to restrict the field-of-view to
prevent unwanted detection of hallway traffic. It
should be positioned at least 6 feet away from HVAC 
registers. Note that whenever the
unit is powered up,
it  will  take  approximately  1  minute 
to begin normal
operation.
OSSNL Wall Switch Occupancy Sensor Wiring Diagram,
Single Location Control
Black (Hot)
Neutral (White)
Load
OSSNL/OSS10
Black
Black
White
White
Blue
Green
Ground
Line
120-230-277VAC, 50/60Hz