Available in 15 or 20 Amp, 125 volt, features self-test
circuitry and slim design. For Residential/Commercial
applications, back and side wired.
Weather-resistant with stainless steel
strap and screws, cold impact resistant
face and button
SAFE — Delivers continuous ground
fault protection
SELF TESTING — Automatically self-tests
to ensure it can respond to ground fault
SIMPLE — Status indicator light
provides simple, intuitive feedback
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
New
210.8(D) GFCI Protection for
Specific Appliances
Change Summary
• GFCI protection is required for the branch circuit or
outlets supplying appliances. The appliances are put
in list format.
NEC
®
Text
Article 210 Branch Circuits Not Over 1000 Volts ac, 1500
Volts dc, Nominal
210.8 Ground-Fault Circuit-Interrupter Protection
for Personnel.
(D) Specic Appliances. GFCI protection shall be provided
for the branch circuit or outlet supplying the following
appliances rated 150 volts or less to ground and 60 amperes
or less, single- or 3-phase:
(1) Automotive vacuum machines
(2) Drinking water coolers and bottle ll stations
(3) High-pressure spray washing machines
(4) Tire ination machines
(5) Vending machines
(6) Sump pumps
(7) Dishwashers
(8) Electric ranges
(9) Wall-mounted ovens
(10) Counter-mounted cooking units
(11) Clothes dryers
(12) Microwave ovens
Expert Analysis
A revision has been made to clarify that GFCI protection
continued on page 20