Instructions / Assembly

EZ-MAX Plus Installation Guide Page 7
Relay Cabinet Mounting
There are several steps required when mounting your relay cabinet:
Step 1: Install the flush mounting kit if appropriate.
Step 2: Plan your conduit runs and electrical room layout.
Step 3: Determine the appropriate methods for mounting your cabinet to the
wall.
Step 4: Mount the cabinet to the wall.
Step 5: Install conduit, pull wire, and other items as required.
Step 6: Proceed to “Line Voltage and Control Power Termination” on page 15.
Selection of a Mounting Location
Choosing a mounting location for your cabinet is critical to the overall success and
ease of installation. Each style of cabinet has its own unique wiring requirements
which must be observed. Please review the next few pages, which describe and
illustrate these requirements.
Suggested Mounting Heights
Although successful operation is completely independent of mounting height, the
suggested mounting heights below were selected to locate the cabinet at a
reasonable and accessible working height.
Environmental Considerations
Cabinets generate heat (see table below). Make sure they are mounted in a
climate controlled space where the temperature will be 0-40
o
C (32-104
o
F) or
20-30
o
C (68-86
o
F) if used as Emergency Lighting Power Equipment.
Reinforce the wall for strength as required for weight and local code.
Clearance on left and right side of the panel should be maintained at 1
1
/
2
" or
greater.
Relays will click while in operation. Locate the panels where audible noise is
acceptable.
Cabinet Suggested Mounting height to bottom of cabinet
8-Relay Cabinet 53" (1,359 mm)
16/24-Relay Cabinet 32" (826 mm)
Cabinet MAX BTU/HR
8-Relay Cabinet 583
16/24 Relay Cabinet 583