Instructions / Assembly

Line Voltage and Control Power Termination Line and Load Circuit Wiring
Page 18
Wiring the Relays
Step 1: Connect the line (feed/circuit breaker) side of the circuit to the “input
terminal(s) on the relay card.
Step 2: Connect the load side of the circuit to the "output" terminal(s) on the
relay card.
Step 3: Please note that relay card terminals accept the following wire sizes:
Figure 7: Wire Sizes and Capacities for Relays
Step 4: Circuit neutrals may follow the path of the line load conductors through
the relay panel or the line/load conductors may pass back to the
panelboard to be joined with the neutral to the load.
Relay Type
(Part #)
Wire Size Wire
Type
Torque
Max Voltage
Tungsten
Rating (120V)
Ballast
Rating
Motor
Rating
(120V/277V)
Inductive Ballast,
Transformer,
HID Rating
30-Amp Relay
(RELAY-030)
1-Pole Relay Module
(RELAY-ST2)
20-8 AWG
Copper
Solid or
Stranded
7 in-lbs 277V 20A 20A 1HP/
2HP
20A
2-Pole Relay Module
(RELAY-2PL)
20-6 AWG
Copper
Solid or
Stranded
20.5 in-lbs 277V
per pole
(480V)
- 20A 2HP 20A
347V Relay Module
(RELAY-347)
20-6 AWG
Copper
Solid or
Stranded
20.5 in-lbs 347V - 20A - 20A
If you need to remove the installed relay cards that shipped
from the factory, remove the shipping screw located near the
connector and discard. This screw is only required for
shipping and not for installation.
MISWIRING THE RELAY MODULES WILL
CAUSE DAMAGE TO THE RELAY MODULE,
THE RELAY CABINET, AND POSSIBLY
OTHER SYSTEMS!
When driving secondary contactors, EMF may
induce significant noise which may cause some
units to reset. Installation of MOV may be
required. Please contact Leviton support for
additional details.