Instructions / Assembly
Photocells Photocell Wiring
Page 36
Figure 20: Switching Photocell
Step 2: Twist strands of each lead tightly (making sure that there are no stray
strands) and push firmly into appropriate plug connector location.
Step 3: Tighten the screws on the plug connector making sure that no bare
conductor is showing.
Step 4: Plug the connector back onto the control module with the screws facing
the front and the wires coming out of the connector toward the top of
the cabinet.
Step 5: If using a switched photocell, make sure that the jumper below the
connector is in the “ON” position.
IN +V COM
Switch Leg
PhotoCell
Switch Leg
AC Power
Note: Switch Legs must be
completly isolated from
Photocell AC power and
should be connected to
either side of the switching
relay at the photocell.
Note: If your switching photo-
cell requires +24VDC power,
this power can be sourced from
the cabinet just like a 0-10VDC
photocell. The switch legs
should still be between COM &
IN terminals