Instructions / Assembly
EZ-MAX Plus Installation Guide Page 39
DIGITAL
Luma-Net III
Luma-Net is Leviton’s proprietary digital architectural lighting control protocol.
Luma-Net can be used for the following items:
• Optional Communication and control by Dimensions 8000 control stations and
accessories.
• Optional Communication and control by Dimensions 4200 control stations and
accessories.
Wiring Specifications
Specification Description
Maximum End to End Run Length 2,000 feet
Maximum number of controlled channels
per subnet
2,048
(when used with a D400 or D800 station)
Maximum number of nodes per subnet on
the network
255
Network Topology Daisy-Chain
Interconnection Method Terminal
Wiring Specifics (1) Twisted Data Pair plus a common
required for digital communication signal
Node power requires additional power
wiring
Supported Voltage +12-24Vdc
Minimum voltages for node functionality varies depending on node type, usually
+10Vdc
Recommended Wire
(includes data and power pair)
Belden 1502R
Belden 1502P (Plenum)
Alternate Approved Wire Belden 9729,9829,8102,9841,
89729,88102
Alpha 6222C, 6412
Network Protocol Leviton Luma-Net
on RS-485
Conflicting or Multiple Control Message
Mitigation Strategy
Last Action Takes Precedence
Termination Requirements Terminate at both ends of control run
Data- to common with 100-120ohm
resistor