FAQ

62
continued from page 61
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
continued on page 64
Revision/New
314.24(B)(C) Box Depth/Conductor
Clearance from Devices - Rear and
Side Entry
Change Summary
• The NEC has set direction on conductors
entering boxes
Article 314 Outlet, Device, Pull, and Junction Boxes;
Conduit Bodies; Fittings; and Handhole Enclosures
314.24 Dimensions of Boxes.
(B) Depth of Outlet and Device Boxes with Enclosed
Devices or Utilization Equipment.
(4) Conductors 12 or 10 AWG. Boxes that enclose
devices or utilization equipment supplied by 12 or 10 AWG
conductors shall have an internal depth that is not less than
30.2 mm (1
3
/
16
in.). Where the equipment projects rearward
from the mounting plane of the box by more than 25 mm
(1 in.), the box shall have a depth not less than that of the
equipment plus 6 mm (1/4 in.). Where wiring enters the
center portion of the rear of a box opposite to the equipment,
the minimum clearance shall be increased to 13 mm
(1/2 in.).
(C) Clearances for Side-Wiring Entrances. Where devices
or equipment are mounted in boxes having side-wiring
entries, the conductors entering from the side shall be
protected as covered in (1) or (2), as follows. The term side
applies to any wall of a box other than the one opposite to
the opening.