Article 210 Branch Circuits Not Over 1000 Volts ac,
1500 Volts dc, Nominal
210.8 Ground-Fault Circuit-Interrupter Protection
for Personnel.
(F) Outdoor Outlets. For dwellings, all outdoor outlets,
other than those covered in 210.8(A), Exception No. 1,
including outlets installed in the following locations, and
supplied by single-phase branch circuits rated 150 volts or
less to ground, 50 amperes or less, shall be provided with
GFCI protection:
(1) Garages that have oors located at or below grade level
(2) Accessory buildings
(3) Boathouses
If equipment supplied by an outlet covered under the
requirements of this section is replaced, the outlet shall be
supplied with GFCI protection.
Exception No. 1 GFCI Protection shall not be required on lighting outlets
other than those covered in 210.8(C)
Exception No. 2 GFCI Protection shall not be required for listed HVAC
equipment. This exception shall expire September 1, 2026
Expert Analysis
A revision has been made to clarify that all outdoor
outlets for dwellings, other than those covered in
210.8(A), Exception No. 1, including outlets installed in
garages that have floors located at or below grade level,
accessory building, or boathouses, are required to have
GFCI protection for personnel.
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.