FAQ

77
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
New
409.70 Surge Protection for Safety
Circuits in Industrial Control Panels
Change Summary
• New section calls for surge protection of safety circuits
within control panels.
Article 409 Industrial Control Panels
409.70 Surge Protection. Safety circuits for personnel
protection that are subject to damage from surge events
shall have surge protection installed within or immediately
adjacent to the control panel.
Expert Analysis
A new section has been added to clarify that surge
protection shall be installed within or immediately
adjacent to the control panel to protect safety circuits
for personnel protection. The surge protective devices
address a documented safety issue that has been
reported by the Electrical Safety Foundation.
Leviton Solution
51120-1
Type 2 Single Phase Surge Panel with 4-Mode Protection
120/240V Single Phase Panel Mount
Surge Protective Device, 4-Mode
Protection, 50kA Max Surge Current
Rating, NEMA 1 Enclosure, UL 1449
4th Edition Type 2.
Leviton’s Surge Protection Devices
can be used individually or as part of
a coordinated application strategy,
to protect sensitive electronic
equipment, in industrial, commercial
and residential locations, from the
stress and degradation inflicted by
voltage transients. Transients are
diverted away from sensitive micro circuitry, providing protection
against catastrophic failure, costly downtime and data disruptions.