FAQ

61
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
comply with the following as applicable.:
(1) Screws shall be machine type with blunt ends.
(2) Other fasteners shall have blunt ends.
(3) Screws attaching a cover shall extend no more than 10
mm (3/8 in.).
(4) Screws or other fasteners, other than in (3), penetrating a
cover shall extend no more than 8 mm (5/16 in.).
(5) Screws or other fasteners penetrating a wall of a box
exceeding 1650 CM
3
(100 in.
3
) shall extend no more than
6 mm (1/4 in.), or more than 11 mm (7/16 in.) if located
within 10 mm (3/8 in.) of an adjacent box wall.
(6) Screws or other fasteners penetrating the wall of a box
not exceeding 1650 CM
3
(100 in.
3
) and not covered in
314.23(B)(1) shall be made ush with the box interior.
(7) Screws or other fasteners penetrating the wall of a
conduit body shall be made ush with the conduit
body interior.
Exception to (3) through (6): A screw shall be permitted to be longer if the
end of the screw is protected with an approved means.
Expert Analysis
A new section has been added to address the
possibility of screws and fasteners damaging conductors
within boxes. In all instances the only permitted style
of screws are the type with machine threads and a
blunt end. This reduces the likelihood of damage to
conductors due to coarse threads and sharp points
typically found on sheet metal screws. The penetrating
length varies depending on the application and location.
Any screw sanctioned by the equipment manufacturer
will be automatically acceptable. Other screws, such as
those used to attach identifying medallions, must have
machine threads and have blunt ends.
continued on page 62