FAQ

74
Expert Analysis
A revision has been made to clarify that receptacles
shall not be installed inside of the tub or shower or
within a zone measured 3 ft (900 mm) horizontally from
any outside edge of the bathtub or shower stall, which
includes the space outside the bathtub, or shower stall,
or within the space below the zone.
A new exception 4 has been added to recognize,
that it is quite common for a toilet to be located next
to a bathtub or shower in a residential bathroom.
Existing text could prevent the installation of a
receptacle, that is necessary for the operation of an
electronic toilet (also known as a “smart toilet”) or
personal hygiene device (e.g., electronic bidet seat)
where a toilet is located within 3 ft (900 mm)
horizontally of a bathtub or shower.
continued from page 73