FAQ

65
Revision/New
334.15(B), 334.19 Protecting Conductors
– Bushings and Sheath Length
Change Summary
• The NEC has added language intended to
protect conductors.
Article 334 Nonmetallic-Sheathed Cable:
Types NM and NMC
334.15 Exposed Work.
(B) Protection from Physical Damage. Cable shall be
protected from physical damage where necessary by rigid
metal conduit, intermediate metal conduit, electrical metallic
tubing, Schedule 80 PVC conduit, RTRC marked with
the sufx -XW, or other approved means. Where passing
through a oor, the cable shall be enclosed in rigid metal
conduit, intermediate metal conduit, electrical metallic
tubing, Schedule 80 PVC conduit, RTRC marked with the
sufx -XW, or other approved means extending at least
150 mm (6 in.) above the oor. Conduit or tubing shall be
provided with a bushing or adapter that provides protection
from abrasion at the point the cable enters and exits
the raceway.
Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar nish.
334.19 Cable Entries. The sheath on nonmetallic-sheathed
cable shall extend not less than 6 mm (1/4 in.) beyond any
cable clamp or cable entry.
Expert Analysis
A new section has been added at 334.15 to ensure
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
continued on page 66