Instructions / Assembly

Single Pole (One location) or 3-Way (Multi-location)
Digital Timer Switch
Cat. No. VPT24-1P, Lighted
LED and CFL Compatible
1800W Incandescent – 15A Fluorescent Ballast – 600W CFL - 5A L.E.D. – 1Hp Motor
120VAC, 60Hz
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
TO AVOID FIRE SHOCK OR DEATH; TURN OFF POWER at circuit breaker or fuse when servicing, installing or removing fixture.
To be installed and/or used in accordance with electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
vizia +™ electronic switches are not compatible with standard 3-way or 4-way switches. They must be used with compatible vizia +™ on/off remotes.
WARNINGS AND CAUTIONS:
Recommended minimum wall box depth is 2-1/2".
Use only one (1) vizia +
TM
digital timer switch in a multi-location circuit with up to 9 coordinating remote switches (without LEDs) or up to 4 matching remote switches (with LEDs)
.
Maximum wire length from digital timer switch to all installed remotes cannot exceed 300 ft (90 m).
Use this device with copper or copper clad wire only.
IMPORTANT : For 3-Way applications, note that one of the screw
terminals from the old switch being removed will usually be a different
color (Black) or labeled Common. Tag that wire with electrical tape and
identify as the common (Line or Load) in both the switch wall box and
remote wall box.
Tools needed to install your Timer Switch
Slotted/Phillips Screwdriver Electrical Tape Pliers
Pencil Cutters Ruler
Hot (Black)
Neutral (White)
Load
Timer Switch
BKWH
Black
Whit
e
RD
Green
Ground
YL/RD
Line
120VAC, 60H
z
Use lead for 3-Way or more
applications only. For single
pole applications, do not
remove the insulating label.
WIRING TIMER SWITCH:
Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to timer switch Green lead.
Line Hot wall box wire to timer switch Black lead.
Load wall box wire to timer switch Red lead.
Line Neutral wall box wire to timer switch White lead.
NOTE: If label is missing place electrical tape around the timer switch
Yellow/Red lead. Ensure no strands are exposed.
Proceed to Step 5.
Hot (Black)
Neutral (White)
Coordinating Remote Switch (no LED)
YL/RD
YL/RD
RD
WH
RD
BK
Black
BKWH
Whit
e
Line
120VAC, 60H
z
Green
Ground
Green
Ground
(unused)
(unused)
Load
Timer Switch
WIRING TIMER SWITCH:
Connect wires per WIRING DIAGRAM as follows:
NOTE: The timer switch must be installed in a wall box that has a Line Hot
connection.
NOTE: Maximum wire length from timer switch to all installed remotes
cannot exceed 300 ft (90 m).
Green or bare copper wire in wall box to timer switch Green lead.
Line Hot (common) wall box wire identified (tagged) when removing old
switch to timer switch Black lead.
First Traveler wall box wire to timer switch Red lead
(note wire color).
Remove Red insulating label from timer switch Yellow/Red lead.
Second Traveler wall box wire to the Yellow/Red lead (note wire
color). This traveler from the timer switch must go to the terminal screw
on the remote marked "YL/RD".
Line Neutral wall box wire to timer switch White lead.
WIRING COORDINATING REMOTE SWITCH (VP0SR-10):
Connect wires per WIRING DIAGRAM as follows:
NOTE: "BK" and "RD" terminals on coordinating remote switch are
unused. Tighten both screws.
NOTE: Maximum wire length from timer switch to last remote cannot
exceed 300 ft (90 m).
Green or bare copper wire in wall box to Green terminal screw.
Load wall box wire identified (tagged) when removing old switch to First
Traveler (note color as above).
Second Traveler wall box wire (note color as above) to terminal screw
marked "YL/RD". This traveler from the remote must go to the Yellow/
Red lead on the timer switch.
Remove White insulating label from terminal screw marked "WH".
Line Neutral wall box wire to terminal screw marked "WH".
Proceed to Step 5.
Installing your Timer Switch
NOTE: Use check boxes when Steps are completed.
WARNING: TO AVOID FIRE SHOCK OR DEATH; TURN
OFF POWER at circuit breaker or fuse and test that power is
off before wiring!
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFFONOFF
ONOFF
ONOFF
ONOFF
ONOFF
Step 1
Identifying your wiring application (most common):
NOTE: If the wiring in your wall box does not resemble any of
these configurations, consult a qualified electrician.
2
4
3
1
2
4
1
5
3
Single Pole
1. Line (Hot)
2. Neutral
3. Ground
4. Load
3-Way
1.
Line or Load
(see important instruction below)
2. Neutral
3. Ground
4. First Traveler – note color
5. Second Traveler – note color.
NOTE: For matching remote
w/LEDs installation, the First
Traveler becomes Line Hot.
Step 2
Green
Yellow/Red
Insulating label:
This wire is used in 3-way installations only.
For single pole installations, do not remove insulating label.
Red
White
Black
1
2
4
3
Single Pole Wiring Application:
Step 4a
2
1
4
BK
RD
YL/RD
Coordinating Remote Switch Timer Switch
5
3
Terminal
Screw marked
White (WH)
Green
Yellow/
Red
Red
White
Black
Terminal
Screw marked
Yellow/Red
(YL/RD)
2
5
1
3
4
WH
3-Way Wiring with Coordinating Remote Switch,
VP0SR-10, (no LED) Application:
Step 4b
Make sure that the ends of the wires from the wall box are
straight (cut if necessary).
Remove insulation from each wire in the wall box as shown.
For Single-Pole Application, go to Step 4a.
For 3-Way Coordinating Remote (no LEDs) Application, go to Step 4b.
For 3-Way Matching Remote (with LEDs) Application, go to Step 4c.
Cut
(if necessary)
Changing the color of your device:
Your device may include color options. To change color of the face,
proceed as follows:
12
PM
A
Th
MENU
SET
12
AM
12
PM
A
Th
MENU
SET
12
AM
Push in side
at tab to release
Line up tabs and
press in sides one at
a time to attach
5/8"
(1.6 cm)
Strip Gage
(measure bare
wire here)
Step 3
Preparing and connecting wires:
Pull off pre-cut insulation from timer leads. Make sure that
the ends of the wires from the wall box are straight (cut if
necessary). Remove insulation from each wire in the wall
box as shown.
WIRE NUT / # OF CONDUCTOR
COMBINATION CHART
1- #12 w/ 1 to 3 #14, #16 or #18
2- #12 w/ 1 or 2 #16 or #18
1- #14 w/ 1 to 4 #16 or #18
2- #14 w/ 1 to 3 #16 or #18
For non-standard wiring applications, refer
to Wire Nut and Conductor Size Chart
3-Way Wiring with Matching Remote Switch,
VP0SR-1L, (w/LED) Application:
Step 4c
BK
RD
YL/RD
Matching Remote Switch Timer Switch
3
5
1
2
4
Green
Yellow/
Red
Red
White
Black
2
5
1
3
4
Additonal Neutral Wire
WH
NOTE: The timer switch must be installed in a wall box that has a Load
connection. The matching remote must be installed in a wall box with
a Line Hot connection and a Neutral connection. A Neutral wire to the
matching remote needs to be added as shown.
If you are unsure about any part of these instructions, consult an
electrician.
NOTE: Maximum wire length from dimmer to all installed remotes cannot
exceed 300 ft (90 m).
WIRING MATCHING REMOTE SWITCH, VP0SR-1L
(wall box with Line Hot connection):
Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to Green terminal screw.
Line Hot (common) wall box wire identified (tagged) when removing
old switch and First Traveler to remote terminal screw marked "BK".
Second Traveler wall box wire from switch to remote terminal screw
marked "YL/RD" (note wire color). This traveler from the remote must
go to the Yellow/Red lead on the timer switch.
Line Neutral wall box wire to remote terminal screw marked "WH".
WIRING TIMER SWITCH (wall box with Load connection):
Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to timer switch Green lead.
Load wall box wire identified (tagged) when removing old switch to timer
switch Red lead.
First Traveler Line Hot to timer switch Black lead.
Remove Red insulating label from Yellow/Red lead.
Second Traveler wall box wire (note color as above) to timer switch
Yellow/Red lead. This traveler from the switch must go to the terminal
screw on the remote marked "YL/RD".
Line Neutral wall box wire to timer switch White lead.
Proceed to Step 5.
Hot (Black)
Neutral (White)
Timer Switch
Black
Whit
e
Line
120
VAC, 60Hz
Load
Green
Ground
Green
Ground
Matching Remote Switch (w/LED)
YL/RD
RD YL/RD
WH
BK
BK
WH
Position all wires to provide
room in outlet wall box for
device.
Ensure that the word “TOP” is
facing up on device strap.
Partially screw in mounting
screws in wall box mounting
holes.
Testing your Switch prior to mounting in
wall box:
Step 5
NOTE: Dress wires with a bend as shown
in diagram in order to relieve stress when
mounting device.
Switch Mounting:
TURN OFF POWER AT CIRCUIT BREAKER OR FUSE.
Installation may now be completed
by tightening mounting screws into
wall box. Attach wallplate.
Step 6
Restore Power:
Restore power at circuit breaker or fuse.
Installation is complete.
NOTE: The Digital Timer Switch is equipped with an internal
rechargeable battery back-up to keep programmed settings
in the event of a power interruption.
Step 7
Restore power at circuit
breaker or fuse.
Wait until or time is
displayed on the screen.
Press pad until locator light is
OFF. Load should turn ON.
If loads do not turn ON, refer
to the TROUBLESHOOTING
section.
Locator LED
DI-000-VPT24-02F