Install Manual

AC Module System Installation Manual
Rev. 1.0
If AC junction box is on the right side of a 2-by-6 PV array in portrait orientation,
An example is described below for a case where a modification of the array design is inevitable because of a roof vent or
other obstacles. The benefit of the AC module comes from a case where a connection of AC modules in reverse position
can be achieved.
If AC junction box is on the left of a 2-by-6 PV array in portrait orientation,
Use proper a transition cable for connecting the array with the AC junction box. (Refer to 3-12 Connecting Array of AC
Modules-to-Distribution Panel guiding installers to make a transition cable from an extension cable) Seal the AC cable
male or female connector of the last AC module using an appropriate end cap. End caps can be found in an extension
cable.
Requirement for the connection of AC modules in reverse position.
Unlike a general connection of AC modules in a portrait orientation, AC modules in a reverse position requires to be
placed with a gap ranging from 6mm(0.24 inch) to 50mm (1.95 inch). Otherwise, the length of the AC cables is not
enough for male and female connectors to be fully connected.
Possible combination of AC modules for array design
32
Copyright © 2017 LG Electronics.
All Rights Reserved.
<1000mm
<39.37 inch
<300mm
<11.81 inch
Female connector
Male connector
F
M