There is a sample for grounding method as described below.
Using ground holes on PV frames
• Determine the size of an external ground wire according to Article 690.45, NEC2014.
(Grounding conductors smaller than 6 AWG shall be protected from physical damages.)
• All dead metal parts should be grounded through the connection of the PV module frame.
• Each grounding point on each PV frame is identified with ground symbol. The ground symbols are found on PV
frame. This marking is etched directly into the aluminum frame.
• The combination of 2 flat washers, star washer, cup washer, spring washer and M4 size nut and bolt made of
stainless steel is required in order to provide a reliable grounding connection to the module frame.
• Use torque under 4-5N•m.
AC junction box
grounding
wire
• LG AC module includes DC cables in the module’s internal wiring, so no grounding is required for DC input.
• LG AC Modules need to be grounded by using an external grounding equipment conductor. LG does not provide
a grounding conductor.
• The grounding method using ground holes on PV frame is tested and qualified by UL.
Electric connection of the PV Rack and
AC Module
Samples for grounding
35
Copyright © 2017 LG Electronics.