Install Manual

AC Module System Installation Manual
Rev. 1.0
There is a sample for grounding method as described below.
Using ground holes on PV frames
Determine the size of an external ground wire according to Article 690.45, NEC2014.
(Grounding conductors smaller than 6 AWG shall be protected from physical damages.)
All dead metal parts should be grounded through the connection of the PV module frame.
Each grounding point on each PV frame is identified with ground symbol. The ground symbols are found on PV
frame. This marking is etched directly into the aluminum frame.
The combination of 2 flat washers, star washer, cup washer, spring washer and M4 size nut and bolt made of
stainless steel is required in order to provide a reliable grounding connection to the module frame.
Use torque under 4-5Nm.
AC junction box
grounding
wire
LG AC module includes DC cables in the module’s internal wiring, so no grounding is required for DC input.
LG AC Modules need to be grounded by using an external grounding equipment conductor. LG does not provide
a grounding conductor.
The grounding method using ground holes on PV frame is tested and qualified by UL.
Electric connection of the PV Rack and
AC Module
Samples for grounding
35