Use and Care Manual

Product Data 36
YA Chassis
PTAC
6RWU0-03A
UYC123ALE31(LP123CD3B)
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
9.89 9.38 0.67 9.69 9.49 0.80 9.23 9.69 0.93
11.55 9.13 0.68 11.30 9.23 0.81 10.77 9.40 0.94
12.88 8.89 0.69 12.61 8.99 0.82 12.02 9.14 0.96
13.48 8.79 0.70 13.20 8.87 0.83 12.58 9.02 0.97
14.80 8.49 0.71 14.48 8.56 0.85 13.80 8.68 0.99
15.36 8.32 0.72 15.03 8.38 0.86 14.32 8.49 1.00
Outdoor Air Temperature : DB°F
68 77 89.6
Indoor Air
Temperature
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
8.95 9.78 0.98 8.62 9.94 1.04 8.34 10.03 1.07
10.45 9.48 0.99 10.06 9.62 1.06 9.73 9.70 1.09
11.66 9.21 1.01 11.22 9.33 1.07 10.86 9.39 1.11
12.20 9.08 1.03 11.75 9.19 1.09 11.36 9.25 1.13
13.39 8.74 1.04 12.89 8.83 1.10 12.47 8.87 1.14
13.89 8.54 1.05 13.38 8.61 1.12 12.94 8.65 1.16
Outdoor Air Temperature : DB°F
95 104 109.4
Indoor Air
Temperature
UYC153ALE31(LP153CD3B)
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
12.25 10.79 0.88 11.99 10.92 1.04 11.42 11.15 1.22
14.29 10.50 0.89 13.99 10.62 1.06 13.33 10.82 1.24
15.94 10.23 0.91 15.61 10.34 1.08 14.87 10.52 1.26
16.69 10.11 0.92 16.33 10.21 1.09 15.56 10.38 1.28
18.31 9.77 0.94 17.93 9.85 1.11 17.08 9.99 1.29
19.01 9.57 0.95 18.60 9.64 1.13 17.73 9.77 1.31
Outdoor Air Temperature : DB°F
68 77 89.6
Indoor Air
Temperature
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
11.08 11.26 1.28 10.67 11.43 1.36 10.32 11.54 1.41
12.93 10.91 1.30 12.45 11.07 1.39 12.04 11.16 1.43
14.43 10.60 1.32 13.89 10.73 1.41 13.44 10.81 1.45
15.10 10.45 1.35 14.54 10.58 1.43 14.06 10.65 1.48
16.57 10.05 1.36 15.96 10.16 1.45 15.43 10.21 1.50
17.20 9.82 1.38 16.56 9.91 1.47 16.02 9.96 1.52
Outdoor Air Temperature : DB°F
95 104 109.4
Indoor Air
Temperature
Symbol Notes
DB : Dry Bulb Temperature [°F] 1. All capacities are net, evaporator fan motor heat is deducted.
WB : Wet Bulb Temperature [°F] 2. Indicates nominal capacity.
TC : Total Capacity [kBtu/h] 3. Direct interpolation is permissible. Do not extrapolate
SHC : Sensible Heating Capacity [kBtu/h]
PI : Power Input [kW]
(Comp.+ indoor fan motor + outdoor fan motor)