Engineering Manual
General Data / Specications
FOUR-WAY VAHU INDOOR UNITS
Model Name LVN180HV4 LVN240HV4 LVN360HV4
Nominal Cooling Capacity (Btu/h)
1
18,000 24,000 36,000
Nominal Heating Capacity (Btu/h)
1
20,000 27,000 40,000
Operating Range
Cooling (°F WB)
57-77 57-77 57-77
Heating (°F DB)
59-81 59-81 59-81
Fan
Type
Sircocco Sircocco Sircocco
Motor Output (W) x Qty.
198 x 1 198 x 1 400 x 1
Motor/Drive
Brushless Digitally
Controlled / Direct
Brushless Digitally
Controlled / Direct
Brushless Digitally
Controlled / Direct
Airflow Rate CFM (H/M/L) at 0.5" WG ESP
640 / 580 / 480 710 / 640 / 480 1,100 / 1,000 / 900
Maximum External Static Pressure (in. WG)
0.7 0.7 1.00
Unit Data
Refrigerant Type
2
R410A R410A R410A
Refrigerant Control
EEV EEV EEV
Power Supply V, Ø, Hz
3
208-230, 1, 60 208-230, 1, 60 208-230, 1, 60
Rated Amps (A)
1.1 1.1 2.2
Sound Pressure Level ±3 dB(A) (H/M/L)
4
at 0.3"WG ESP
42 / 42 / 41 43 / 42 / 41 45 / 44 / 43
Dimensions (W x H x D, in.)
18 x 48-11/16 x 21-1/4 18 x 48-11/16 x 21-1/4 25 x 55-3/16 x 21-1/4
Net Weight (lbs.)
129 129 165
Shipping Weight (lbs.)
140 140 188
Power Wiring / Communications Cable (No. x AWG)
5
4 x 18 4 x 18 4 x 18
Heat Exchanger
(Row x Column x Fin / inch) x Number
(3x 24 x 18) x 2 (3x 24 x 18) x 2 (3x 30 x 18) x 2
Pipe Size
Liquid (in.)
1/4 1/4 3/8
Vapor (in.)
1/2 1/2 5/8
Connection Size
Liquid (in.)
3/8 3/8 3/8
Vapor (in.)
5/8 5/8 5/8
Primary Drain I.D. (in.)
3/4 FPT 3/4 FPT 3/4 FPT
Secondary Drain I.D. (in.)
3/4 FPT 3/4 FPT 3/4 FPT
Table 91: Multi F Vertical-Horizontal Air Handling Indoor Unit General Data.
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
This unit comes with a dry helium charge.
3
Acceptable operating voltage: 187V-253V.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
All power wiring / communications cable to the IDUs must be minimum 18 AWG, 4-conductor, stranded,
shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
applicable local and national codes.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
158 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual