Installation Manual

Installation Manual 21
Installation
ENGLISH
LGAP Network System
Master
Master
Slave
GND
Signal
12 V
Slave
Slave
Slave
or
Display Error Message
4. 2 Remote Control
n Wired remote controller 2 + Indoor unit 1
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit.
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired
remote controller.
6. There isnʼt limits of indoor unit function.
Indoor unit 2 EA +Wired remote controller 1 EA
Indoor unit 1 EA +Wired remote controller 2 EA
h
PZCWRCG3 cable used for connection
h
PZCWRC2 cable used for connection
Slave
Master
Master
PZCWRCG3
Master Slave
PZCWRC2
5. Accessories for group control setting
It is possible to set group control by using below accessories.