Installation Manual

Installation Manual 23
How to Set E.S.P?
ENGLISH
How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the
installation of the product. Otherwise, there is a risk of weak cooling/heating and
condensed water discharge/drop.
M1 Chassis : 7, 9, 12, 15, 18 k
M1 Chassis : 24 k
(Unit: CMM)
(Unit: CMM)
Setting
value
Static Pressure (mmAq(in wg))
2.5(0.10) 4(0.16) 6(0.24) 8(0.31) 10(0.39) 12(0.47) 14(0.55) 15(0.59)
60 6.6(233)
65 8.9(315)
70 11.3(400) 8.1(285)
75 12.9(455) 10.4(368) 6.1(216)
80 14.7(520) 12.5(440) 8.4(296)
85 16.4(580) 14.3(504) 10.4(366)
90 18.1(640) 16.1(569) 12.9(454) 8.9(314)
95 19.7(696) 17.9(631) 15.0(530) 11.7(413)
100 20.9(737) 19.3(681) 16.9(598) 14.4(509) 9.7(344)
105 23.1(816) 21.4(755) 18.9(666) 16.1(570) 12.0(423) 7.4(260)
110 24.4(860) 22.9(809) 20.7(731) 18.5(652) 15.2(538) 9.9(351)
115 24.3(858) 22.3(786) 20.2(715) 17.6(621) 14.3(506) 9.5(334)
120 23.8(841) 21.9(775) 19.5(687) 16.5(581) 12.8(452) 10.0(352)
125 23.6(833) 21.5(761) 19.1(675) 16.1(569) 14.2(501)
130 25.7(906) 23.4(828) 21.0(742) 18.2(644) 16.7(590)
135 25.2(890) 23.2(819) 20.8(735) 19.4(684)
140 25.1(888) 23.2(820) 21.8(770)
Setting
value
Static Pressure (mmAq(in wg))
2.5(0.10) 4(0.16) 6(0.24) 8(0.31) 10(0.39) 12(0.47) 14(0.55) 15(0.59)
60 16.2(572) 14.4(510)
65 17.7(625) 15.8(558)
70 18.9(667) 17.4(615) 14.6(515)
75 20.3(717) 18.9(668) 16.7(588) 14.0(494)
80 21.8(770) 20.1(710) 17.9(633) 15.7(554) 12.5(440)
85 23.2(819) 21.8(769) 19.6(692) 17.4(616) 14.3(506)
90 24.7(872) 23.4(825) 21.4(755) 19.5(687) 16.9(598) 13.8(487)
95 25.8(911) 24.6(868) 22.8(805) 21.0(742) 18.6(658) 15.7(553) 10.7(378)
100 25.9(916) 24.3(858) 22.6(798) 20.5(723) 17.9(631) 14.3(504) 11.8(418)
105 25.5(900) 24.0(848) 22.2(784) 20.1(710) 17.5(618) 15.9(560)
110 25.3(894) 23.9(844) 22.3(786) 20.2(713) 18.8(664)
115 25.0(884) 23.5(830) 21.6(764) 20.6(728)