Installation Manual

How to Set E.S.P?
26 Indoor Unit
• This function automatically sets the rotation speed of the fans corresponding to each step of
rated airflow for easy installation.
Auto ESP setting is required by remote control
<Type 1>
1. If
B
button is pressed so long for over 3 seconds, it enters to the installer setting mode.
2. Use the
FG
buttons to enter 68-02 and set the Value2 value.
Refer to the table below for Value2 values. (It takes approximately 3 to 8 minutes.)
3. Once the set-up is complete, you can enter installer setup (68) to check whether the set-up
has succeeded or failed. (03: Success, 04: Failure)
For details, refer to the remote control manual
Value 1
(Auto ESP mode)
Value 2
(Manual Step)
Description
(Voltage setting)
ëë
(Not use)
--
ëâ
(Auto)
--
ëã
(Manual)
ë
190 V
â
200 V
ã
210 V
ä
220 V
å
230 V
æ
240 V
ç
250 V
è
260 V
é
270 V
ëä
-
Cannot be set, only monitoring is possible.
If the value1 is 03, setting is successful.
ëå
-
Cannot be set, only monitoring is possible.
If the value1 is 04, setting has failed.
Value 2 : Manual step
Value 1 : Auto ESP mode
Code value
How to Set Auto ESP (Air conditioner)