Installation Manual

10 Indoor Unit
Installation
Set screw of
paper model (4 pieces)
Paper model
for installation
Ceiling board
55mm
(2-3/16 inch)
Adjust the same height
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm(1-1/2 inch)
Open the ceiling board
along the outer edge of the
paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
• The following parts are local purchasing.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
Terminal Block Indoor
1(L1) 2(L2) 3(A) 4(B)
INDOOR POWER INPUT
A-- ----BAB
GND 12V
DRY2DRY1
INTERNETIDUSODU
Outdoor
Unit
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Wiring Connection
WARNING : Make sure that the screws of the terminal are free from looseness.
WARNING : Loose wiring may cause the terminal to overheat or result in unit malfunction.
A fire hazzard may also exist.
Therefore, be sure all wiring is tightly connected.
CAUTION : Tighten the nut and bolt to
prevent unit from falling off.
Connection method of the connecting cable(Example)
1(L1) 2(L2)
3(A)
4(B)
Power Supply
High Voltage
(208/230V)
Transmission
Lock nut
Conduit
mounting
plate
Conduit