Installation Manual

12 Indoor Unit
Installation
• Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is
32mm(1-1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe 25mm(1 inch)
and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
Feed water to the flexible drain hose and
check the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring
is complete.
• When the test is complete, connect the flex-
ible drain hose to the drain port on the
indoor unit.
Heat insulation material: Polyethylene foam with thick-
ness more than 8mm(5/16 inch).
Drain test
Flexible drain hose
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
(27-9/16 inch)
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
1/50~1/100
MAX 700mm
(27-9/16 inch)
Flexible drain hoseFlexible drain hose
Drain Piping
CAUTION : The supplied flexible drain
hose should not be curved, neither
screwed. The curved or screwed hose
may cause a leakage of water.