Installation guide
18 Outdoor Unit
Installation
Installation
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm(3-15/16 inch) under the units legs before
being fixed.
• The outdoor unit supports should have minimum height of 200mm(7-7/8 inch).
• Anchor bolts must be inserted at least 75mm(2-15/16 inch).
At leas
t 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
Needed for outdoor units of 8Hp or above
Center of the Unit
The outdoor unit should
not be supported only by
the corner supports.
Needed for outdoor units of 8Hp or above
Center of the Unit
730(28-3/4)
760(29-29/32)
65(2-9/16)
65(2-9/16)
Unit : mm(inch)
At least
65(2-9/16)
At least
65(2-9/16)
Chassis
Outdoor unit capacity
A [mm(inch)] B [mm(inch)]
H/R
UX2 8HP 920(36-7/32) 792(31-3/16)
UX3 10~14HP 1240(48-13/16) 1102(43-3/8)