Submittal Sheet

ARVU053ZEA2
EnergyRecoveryVentilator(ERV)
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
(Company)
(ProjectManager)
Tag#:
Performance:
Electrical:
NominalCapacity(CFM)
470
PowerInputSH(W)
360
RatedAmpsSH(A)
2.8
PowerSupply(V/Hz/Ø)
208230/60/1
UnitData:
Fan:
Type
CrossFlow
Quantity
2
Motor/Drive
BrushlessDigitallyControlled/Direct
Filter
Washable
NetUnitWeight(lbs)
148
AirflowRateSH/H/L(CFM)
471/471/388
ExternalStaticPressureSH/H/L(inwg)
0.80/0.44/0.24
SoundPressureSH/H/LdB(A)
40/37/31
Notes:
1.SH=superhighspeed,H=highspeed,L=lowspeed
2.Allcommunicaoncabletobeminimum18AWG,2conductor,stranded,shieldedandmust
complywithapplicablelocalandnationalcode.
3.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
4.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
.
VentilationNormal
(
B
yp
ass
)
Mode:
Page1of2
VRFSBDT001US014B11
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
ControlsFeatures:
AirtoAirHeatExchanger
Crossflowfixedcore
EnthalpyExchangeEfficiency(%)
Cooling(fanspeedSH)
37
Heating(fanspeedSH)
52
HeatExchangerData:
O
p
eratin
g
Ran
g
e:
OutdoorTemperature(°FDB)
14113
Quantity
1
Quantity
2
StandAloneMode:
•Canbeoperatedindependently
•Drawsoutdoorairandindoorexhaustairacrossairtoair
heatexchanger
VentilationHeatExchan
g
eMode:
ShippingWeight(lbs)
177
TemperatureExchangeEfficiency(%)
Cooling(fanspeedSH)
62
Heating(fanspeedSH)
61
Capacitiesareinaccordan cewithAHRIStandard1060.
•Controlsbypassdampertobypassairtoairheatexchanger
anddrawinuntemperedoutdoorair
O
p
tionalAccessories:
LGProgrammableThermostat‐PREMTB10U
PI485(requiredforcentralcontroller)‐PSNFP14A0