Installation guide
46
INSTALLATION
ENGLISH
Pressure Drop
NOTE
!
• To secure enough water flow rate, do not set water pump capacity as Minimum.
It can lead unexpected flow rate error CH14.
NOTE
!
When installing the product, install additional pump in consideration of the pressure loss and
pump performance.
If flow rate is low, overloading of product can occur
Capacity
Rated flow-rate
[LPM, m
3
/h]
Pump Head [m]
(at rated flow-
rate)
Product pressure
drop [m]
(Plate heat
exchanger)
Serviceable Head
[m]
16 kW 46.0 (2.8) 9.0 1.4 7.6
14 kW 40.25 (2.4) 9.3 1.1 8.2
12 kW 34.5 (2.1) 9.8 0.8 9.0
9 kW 25.87 (1.5) 6.1 0.4 5.7
7 kW 20.12 (1.2) 7.3 0.3 7.0
5 kW 14.37 (0.9) 7.5 0.2 7.3
Water pump Capacity
The water pump us variable type which is capable to change flow rate, so it may be required to
change default water pump capacity in case of noise by water flow. In most case, however, it is
strongly recommended to set capacity as Maximum.