Installation guide
53
ACCESSORIES INSTALLATION
ENGLISH
1.5 m
Direct
Sun ray contact area
no
no
no
yes
General Information
The Heat Pump supports following thermostats.
(1) There is no electric circuit inside the thermostat and electric power supply to the thermostat is
not required.
(2) Electric circuit such as display, LED, buzzer, etc is included in the thermostat and electric
power supply is required.
(3) Thermostat generates "Heating ON or Heating OFF" signal according to user"s heating target
temperature.
(4) hermostat generates both "Heating ON or Heating OFF" and "Cooling ON or Cooling OFF"
signal according to user"s heating and cooling target temperature.
YesHeating / Cooling (4)
YesHeating / Cooling (4)
YesHeating Only (3)
230 V~
Electrical
(2)
YesHeating Only (3)
230 V~
Mechanical
(1)
SupportedOperating ModePowerType
CAUTION
Choosing heating / cooling thermostat
• Heating / cooling thermostat must have "Mode Selection" feature to distinguish operation
mode.
• Heating / cooling thermostat must be able to assign heating target temperature and
cooling target temperature differently.
• If above conditions are not kept, the unit can not operation properly.
• Heating / cooling thermostat must send cooling or heating signal immediately when
temperature condition is satisfied. No delay time while sending cooling or heating signal is
permitted.
!