Installation guide

144
COMMISSIONING
ENGLISH
Display
code
Title Cause of error Check point & Normal condition
73
AC input instant over
current error
(Matter of software)
(HM**1M U*3) PCB(Inverter) input
power current is over 48A(Peak) for
2ms.
(HM**3M U*3) PCB(Inverter) input
power current is over 27A(Peak) for
2ms.
1. Overload operation (Pipe clogging/Covering/EEV
defect/Ref.overcharge)
2. Compressor damage (Insulation damage/Motor
damage)
3. Input voltage abnormal
4. Power line assemble condition abnormal
5. PCB assembly 1 damage (input current sensing part)