Installation guide

69
ACCESSORIES INSTALLATION
ENGLISH
How to install DHW tank kit
Fellow bellow procedures Spet 1 ~ Step 6
Step 1. Find magnetic switch and ELB(MCCB) in the kit. Fit them into the indoor unit control box
with enclosed a braket and screws.(symbol at picture)
Step 2. Contact ‘CN_B/HEAT(A)’(white connector)of the indoor unit PCB with magnetic switch
contact using encolsed cable(symbol at the picture). Connect magnetic switch
contactor port no. A1 and A2.
Step 3. Connect magnetic switch contactor port no.L1 and L3 with ELB(MCCB) port no. 2 and
4(symbol at the picture).
CAUTION
Check Poarity
• Connect magnetic switch contact port no. L1 to ELB(MCCB) port no.2
• Connect magnetic switch contact port no. L3 to ELB(MCCB) port no.4
!
Step 4. Connect magnetic switch contactor port no. T1 and T3 with terminal block 1 port 6 and
7(symbol at the picture).
Check Polarity
- Connect magnetic switch contact port no. T1 to terminal block 1 port 6
- Connect magnetic switch contact port no. T3 to terminal block 1 port 7
Step 5. Connect ELB(MCCB) to Terminal Block.
1Ø Electric Heater Model
Connect ELB(MCCB) port no.1 and 3 with terminal block 3 port 3 and 4(symbol at the
picture).
3Ø Electric Heater Model
Connect ELB(MCCB) port no.1 and 3 with terminal block 3 port 1 and 2
(symbol at the picture).