Engineering Manual

Table Of Contents
MULTI
F
MAX
MULTI
F
Refrigerant Flow Diagrams
Figure 159: LMHN240HV and LMHN360HV Refrigerant Flow Diagram.
Table 60: Multi F Ceiling-Concealed Duct (High Static) Indoor Unit Refrigerant Pipe Connection Port Diameters.
Model No. Vapor (inch) Liquid (inch)
LMHN240HV Ø1/2 Ø1/4
LMHN360HV Ø5/8 Ø3/8
Table 61: Multi F Ceiling-Concealed Duct (High Static) Indoor Unit Thermistor Details.
Description (Based on Cooling Mode) PCB Connector
Indoor Air Temperature Thermistor CN-ROOM
Evaporator Inlet Temperature Thermistor CN-PIPE/IN
Evaporator Outlet Temperature Thermistor CN-PIPE/OUT
Sirocco Fan
Heat exchanger
Gas pipe connection port
(flare connection)
Liquid pipe connection port
(flare connection)
Cooling
Heating
M
Thermistor for
suction air
temperature
Thermistor for
evaporator outlet
temperature
Thermistor for
evaporator inlet
temperature
DUCT (HIGH STATIC) INDOOR UNITS
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
118 | DUCT (HIGH STATIC)
Multi F and Multi F MAX Indoor Unit Engineering Manual