Multi F Engineering Manual
Table Of Contents
Figure 50: Multi F LMU303HV and LMU363HV System Power Wiring and Communications Cable.
6\VWHPVIRU0XOWL)
ELECTRICAL CONNECTIONS
Outdoor Unit
L(L1)
3(A) 3(C) 3(D)3(B)
Outdoor Unit Terminal Block
L1
L1
L2
L2
G
Power Supply
Main Switch
Circuit Breaker
Fuse
Three-wire Power Wiring
(Including Ground)
COMMUNICATIONS CABLE
POWER WIRING
1(L1) 2(L2)
Indoor Unit Terminal Block
Unit A Unit B Unit C Unit D
3
1(L1) 2(L2) 3 1(L1) 2(L2) 3 1(L1) 2(L2) 3
Indoor Unit Terminal Block Indoor Unit Terminal Block
Indoor Unit Terminal Block
G
G
GG
G
N(L2) L(L1) N(L2) L(L1) N(L2) L(L1) N(L2) L(L1) N(L2)
• All field-supplied wiring, components, and materials must comply with all applicable national, state, and local codes and requirements.
Improper wiring will result in fire, electric shock, causing physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. 'RQRWFRQQHFWWKHJURXQGOLQHWRWKHSLSHV7KHUHLVDULVNRI¿UHHOHFWULFVKRFNH[SORVLRQUHVXOWLQJLQSK\VLFDO
injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. There is a risk of fire, electric shock, explo-
sion, resulting in physical injury or death.
• Terminal block labels, appearances, and location will vary depending on outdoor unit model.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
NOTE
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and require-
ments. Failure to install proper electrical components can result in property damage and equipment malfunction.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper
ground wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components
will result in property damage and equipment malfunction.
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
ELECTRICAL CONNECTIONS | 59