74 | STD. WALL-MOUNTED
Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI
F
MAX
MULTI
F
General Data / Specications
Model Name LQN090HV4 LQN120HV4 LMQN150HV
Nominal Cooling Capacity (Btu/h)
1
9,000 12,000 15,710
Nominal Heating Capacity (Btu/h)
1
10,500 13,650 17,070
Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Fan
Type
Turbo
Motor Output (W) x Qty.
48 x 1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate CFM (Max/H/M/L)
304 / 300 / 237 / 177 346 / 318 / 244 / 184 388 / 357 / 304 / 254
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
EEV
Power Supply V, Ø, Hz
3
208-230, 1, 60
Rated Amps (A)
0.7
Sound Pressure Level dB(A) (H/M/L)
4
38/32/27 39/32/27 44/39/35
Dimensions (W x H x D, in.)
27-9/16 x 23-5/8 x 8-9/32
Net Unit Weight (lbs.)
35.7
Shipping Weight (lbs.)
41.7
Power Wiring / Communications Cable (No. x AWG)
5
4 x 14
Heat Exchanger (Row x Column x FPI ) x Qty.
(2 x 19 x 19 ) x 1
Pipe Size
Liquid (in.)
1/4 1/4 1/4
Vapor (in.)
3/8 3/8 1/2
Connection Size
Liquid (in.)
1/4 1/4 1/4
Vapor (in.)
3/8 3/8 1/2
Drain O.D. / I.D. (in.)
27/32, 5/8
Table 34: Multi F Low Wall Console Indoor Unit General Data.
LOW WALL CONSOLE INDOOR UNITS
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in
accordance with low length of each outdoor unit and a 0 ft. level difference between outdoor and indoor
units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
This unit comes with a dry helium charge.
3
Acceptable operating voltage: 187V-253V.
4
Sound pressure levels are tested in an anechoic chamber under ISO Low 3745 and are the same in
both cooling and heating mode. These values can increase due to ambient conditions during operation.
5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
applicable local and national codes.