16 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
General Data
MULTI F OUTDOOR UNIT
Table 8: /08+9 (I¿FLHQF\ 5DWLQJV
1,2
Table 9: /08+9 (I¿FLHQF\ 5DWLQJV
1,2
System Combined With
Rated Cooling
Capacity (Btu/h)
EER2
(95°F)
SEER2
Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF2
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU243HV
Non-Ducted
Indoor Units
24,000 12.5 22.5 24,600 4.20 9.4 14,900 2.93
Ducted Indoor Units 22,000 12.5 18.5 23,000 3.47 9.0 14,600 2.85
Mixed Non-Ducted and
Ducted Indoor Units
23,000 12.5 20.5 23,800 3.81 9.2 14,750 2.88
System Combined With
Rated Cooling
Capacity (Btu/h)
EER2
(95°F)
SEER2
Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF2
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU183HV
Non-Ducted
Indoor Units
18,000 13.5 22.5 22,000 3.60 9.6 13,800 2.70
Ducted Indoor Units 17,200 12.5 18.5 20,000 3.41 9.0 13,400 2.58
Mixed Non-Ducted and
Ducted Indoor Units
17,600 13.0 20.5 21,000 3.50 9.3 13,600 2.64
1
Capacity is rated 0 ft. above sea level, with a 0 ft. level difference between outdoor and indoor units, and the following refrigerant pipe lengths:
LMU180HV: 16.4 ft. x 2 = 32.8 ft.
LMU240HV: 16.4 ft. x 3 = 49.2 ft.
LMU303HV: 16.4 ft. x 4 = 65.6 ft.
LMU363HV: 16.4 ft. x 4 = 65.6 ft.
All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions
of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB) and outdoor ambient conditions
of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
5DWHGFDSDFLW\LVFHUWL¿HGXQGHU$+5,6WDQGDUG((56((5&23DQG+63)DUHVXEMHFWWRFKDQJH6HHZZZDKULQHWRUJIRUWKH
latest values.
At least two indoor units must be connected. For allocated capacity information, see the combination tables in the "Multi F / Multi F MAX Combina-
tion Data Manual" on www.lghvac.com. For performance data, see "Multi F / Multi F MAX Performance Data Manual" on www.lghvac.com.
System Combined With
Rated Cooling
Capacity (Btu/h)
EER2
(95°F)
SEER2
Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF2
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU363HV
Non-Ducted
Indoor Units
32,800 12.5 21.5 36,000 3.85 9.0 21,000 2.70
Ducted Indoor Units 30,800 11.7 18.0 34,000 3.64 8.6 20,000 2.55
Mixed Non-Ducted and
Ducted Indoor Units
31,800 12.1 19.8 35,000 3.75 8.8 20,500 2.68
System Combined With
Rated Cooling
Capacity (Btu/h)
EER2
(95°F)
SEER2
Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF2
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU303HV
Non-Ducted
Indoor Units
30,000 13.0 22.0 32,000 4.01 9.2 20,000 2.73
Ducted Indoor Units 27,400 12.0 18.5 30,000 3.75 8.8 18,000 2.64
Mixed Non-Ducted and
Ducted Indoor Units
28,700 12.5 20.3 31,000 3.88 9.0 19,000 2.76
Table 10: /08+9 (I¿FLHQF\ 5DWLQJV
1,2
Table 11: /08+9 (I¿FLHQF\ 5DWLQJV
1,2