Multi F Engineering Manual

MULTI F MAX BD UNIT
General Data
Table 32: Multi F MAX BD Unit General Data.
1
At least one Branch Distribution Unit is required for system operation; a maximum of two can be installed per outdoor unit with use of Y-branch accessory (PMBL5620) To connect only one (1) indoor unit to a
branch distribution unit, the system must include another branch distribution unit with at least one (1) connected indoor unit.
2
Branch Distribution Unit can accommodate from one (1) indoor unit up to four (4) indoor units depending on the ports available on the Branch Distribution Unit.
3
All power wiring / communication cable to be minimum 14 AWG, 4-conductor from the outdoor unit to the BD unit (Multi F MAX systems only), and 14 AWG, 4-conductor from the BD unit to the indoor unit,
stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
4
Piping lengths are equivalent.
Model Number PMBD3620 PMBD3630 PMBD3640 PMBD3641
No. of Connectable Indoor Units
1
1-2 1-3 1-4 1-4
Max. Nominal Capacity / Port (Btu/h)
2
24,000 24,000 24,000
Ports A, B, C: 24,000;
Port D: 36,000
Connected Indoor Unit Capacity (Btu/h)
7,000 ~ 24,000 7,000 ~ 24,000 7,000 ~ 24,000
Ports A, B, C: 7,000 ~ 24,000;
Port D: 24,000 or 36,000
Max. Nominal Capacity / Branch Distribution Unit
(Btu/h)
48,000 72,000 73,000 73,000
Operation Temperature Range (°F DB)
0 ~ 150 0 ~ 150 0 ~ 150 0 ~ 150
Maximum Humidity
80% 80% 80% 80%
Unit Data
Refrigerant Type
R410A R410A R410A R410A
Power Supply V, Ø, Hz
208-230, 1, 60 208-230, 1, 60 208-230, 1, 60 208-230, 1, 60
Power Input (W)
16 24 32 32
Rated Amps (A)
0.08 0.12 0.16 0.16
Dimensions W x H x D (in.)
17-3/32 x 6-13/32
x 10-23/32
17-3/32 x 6-13/32
x 10-23/32
17-3/32 x 6-13/32
x 10-23/32
17-3/32 x 6-13/32 x 10-23/32
Net Unit Weight (lbs.)
13 14.3 15.7 15.7
Shipping Weight (lbs.)
15 17 18 18
Communication / Connection (Power) Cables
3
From Outdoor Unit to Branch Distribution Unit
(Qty. x AWG)
3
4C x 14 4C x 14 4C x 14 4C x 14
From Branch Distribution Unit to Indoor Unit
(Qty. x AWG)
3
4C x 14 4C x 14 4C x 14 4C x 14
Piping Connections
Outdoor Unit to
Branch Distribution
Unit
Liquid (in., OD)
Ø3/8 Ø3/8 Ø3/8 Ø3/8
Vapor (in., OD)
Ø3/4 Ø3/4 Ø3/4 Ø3/4
Branch Distribution
Unit to Indoor
Units
Liquid (in., OD) x Qty.
Ø1/4 x 2 Ø1/4 x 3 Ø1/4 x 4 Ø1/4 x 4
Vapor (in., OD) x Qty.
Ø3/8 x 2 Ø3/8 x 3 Ø3/8 x 4 Ø3/8 x 3; Ø1/2 x 1
Piping Lengths
Maximum Total System Piping (ft.)
4
475.7 475.7 475.7 475.7
Maximum Main Pipe Length (Outdoor Unit
to Branch Distribution Units [ft.])
180.4 180.4 180.4 180.4
Total Branch Piping (Branch Distribution Units
to Indoor Units [ft.])
295.3 295.3 295.3 295.3
Maximum Branch Pipe Length Between
Branch Distribution Unit and Each Indoor Unit [ft.])
49.2 49.2 49.2 49.2
Maximum Outdoor Unit to Indoor Unit
Pipe Length (ft.)
229.6 229.6 229.6 229.6
Piping Length (No Additional Refrigerant [ft.];
approx. 16.4 ft. or 49.2 ft. of Main Piping
(depending on ODU model) + 131.2 ft. of Branch
Piping)
147.6 or 180.4
(Depending on
ODU Model)
147.6 or 180.4
(Depending on
ODU Model)
147.6 or 180.4
(Depending on
ODU Model)
147.6 or 180.4
(Depending on
ODU Model)
Maximum Elevation between Branch Distribution
Unit and Indoor Unit (ft.)
32.8 32.8 32.8 32.8
Maximum Elevation between Branch Distribution
Unit and Branch Distribution Unit (ft.)
49.2 49.2 49.2 49.2