INSTALLING MULTI F SYSTEMS
Connection sockets (included as a factory-supplied accessory with the
LQGRRUXQLWVZLOOQHHGWREHXVHGZKHQSLSLQJWKHLQGRRUXQLWVWRWKHRXW-
door unit. See tables above and below for indoor unit piping connection
and connection socket dimensions.
Table 21: Outdoor Unit Piping Connections.
Figure 45: Multi F Refrigerant Pipe Connections
(LMU363HV shown as example).
Avoid Pipe Damage
:KHQURXWLQJILHOGSURYLGHGSLSLQJ avoid damaging the outdoor unit from excessive
vibration.
Properly insulate the liquid and gas lines separately up to the point of connection at the
unit frame.
See table below for Multi F outdoor unit connection types.
Main gas
valve
Main liquid
valve
Gas Piping Connections
Liquid
Piping
Connections
A-UNIT
B-UNIT
C-UNIT
D-UNIT
Indoor Unit Capacity
Vapor (in., OD)
Liquid (in.,
OD)
A B A B
18,000 Btu/h: Wall-Mounted
ĺĺ
Ø5/8
ĺ
15,000 Btu/h: Console;
18,000 Btu/h: Low Static
Duct, Four-Way Cassette,
VAHU
ĺ N/A
24,000 Btu/h ĺ N/A
Multi F Outdoor Unit to Indoor Unit Piping Connections
Outdoor Unit Piping Connections LMU183HV LMU243HV LMU303HV LMU363HV
Liquid Line Connection (in., OD) x Qty. 1/4 x 2 1/4 x 3 1/4 x 4 1/4 x 4
Vapor Line Connection (in., OD) x Qty. 3/8 x 2 3/8 x 3 3/8 x 4 3/8 x 4
Table 22: Indoor Unit Pipe Sizes.
Indoor Unit Capacity
Vapor Line
Piping Size (in., OD)
Liquid Line
Piping Size (in., OD)
7,000 Btu/h
Ø3/8
Ø1/4
9,000 Btu/h
12,000 Btu/h
15,000 Btu/h
15,000 Btu/h: Console;
18,000 Btu/h
Ø1/2
24,000 Btu/h
Table 23: Indoor Unit Piping Connections.
Indoor Unit Capacity
Vapor Line
Conn. (in., OD)
Liquid Line
Conn. (in., OD)
7,000 Btu/h
Ø3/8 Ø1/4
9,000 Btu/h
12,000 Btu/h
15,000 Btu/h
18,000 Btu/h: Wall-Mounted Ø5/8 Ø3/8
15,000 Btu/h: Console;
18,000 Btu/h: Low Static Duct,
Four-Way Cassette, VAHU
Ø1/2 Ø1/4
24,000 Btu/h Ø1/2 Ø1/4
Correctly route the piping so it does not make contact with mounting bolts. Allow room
IRU¿HOGLQVWDOODWLRQ
Table 24: Connection Socket Dimensions.