LGRED Heat General Service Manual

Part 5. Trouble Shooting
- 85 -
Copyright ©2017 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
62
Heatsink High error
Inverter PCB heatsink
temperature is over 85°C
1. ODU fan locking
2. Heatsink assembly of INV PCB assemble condi-
tion abnormal
3. Defect of temperature sensing circuit part defect
of INV PCB
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
Is Installation
Condition Normal?
No
1. Check Pipe Clogging/ Distortion
2. Check Covering (Outdoor/Indoor Unit)
3. Check EEV Connector Assemble Condition/Normal Operation
4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Reassemble or Manage if abnormality Found
1. Check Inv. PCB Screw Connection Condition
Reassemble or Manage if abnormality Found
No
Inv. PCB IGBTM Connection
Condition Normal?
Yes
1. Check Outdoor Unit Fan Motor Operation or Lock
Reassemble or Manage if abnormality Found
No
Is ODU Fan Motor Normal?
Yes
1. Reset
Replace Inv. PCB Assembly
No
Is Inv. PCB assembly
Normal?
Yes
Recheck Power and
Installation Condition
Yes
Check Point
1. Check resistance between No.19 pin and NO.20 pin of PCB PFC module
2. Resistance value should be in 7kΩ ±10%.(at 25°C).
3. Check Inv. PCB Screw Connection Condition – only 36,42kBtu/h class