LGRED Heat LMU180HHV Installation Manual

MULTI
F
MAX
MULTI
F
WITH
13
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 4: Multi F MAX with LGRED Electrical Data.
GENERAL DATA
Multi F MAX with LGRED Outdoor Unit Electrical Data
Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Unit Fan Motor(s)
Indoor Unit
Fan Motor
kW x Quantity FLA x Quantity FLA
3.0 LMU360HHV
60 208 - 230 187 - 253
30.2 45 1 20.4 0.12 x 2 0.73 x 2 3.2
3.5 LMU420HHV 30.2 45 1 20.4 0.12 x 2 0.73 x 2 3.2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.