SPECIFICATIONS
PREMTBVC0 and PREMTBVC1
Dimensions
Height: 4.72 in
Width: 3.39 in
Depth: 1.06 in
Power Requirements
12 VDC, 2.34W, supplied by IDU
Operating Conditions
32 °F - 122 °F
0% - 95% R.H. non-condensing
Storage Conditions
-22 °F - 122 °F
0% - 95% R.H. non-condensing
Temperature Sensor
Local 10 K NTC type 2 thermistor
Temperature Sensor Resolution
± 0.2 °F
Temperature Control Accuracy
± 0.9 °F @ 70 °F, typical calibrated
Humidity Sensor and Calibration
Single point calibrated bulk polymer type sensor
Humidity Sensor Precision
Reading range from 10-90 % R.H. non-condensing,
10 to 20% precision: 10%
20% to 80% precision: 5%
80% to 90% precision: 10%
Humidity Sensor Stability
Less than 1.0 % yearly (typical drift)
Dehumidification Setpoint Range
30% - 95% R.H.
Occ, Stand-By and Unocc Cooling Dual Setpoint Range
52 - 99 °F
Occ, Stand-By and Unocc Heating Setpoint Range
40 °F - 90 °F